beautypg.com

4 supply air discharge, 0 mechanical (cont'd), 3 unit inlet air (cont'd) – Reznor RPB Unit Installation Manual User Manual

Page 20

background image

Form I-RPB, P/N 131782 R11, Page 20

6.3.4 Evaporative Cooling Module, Option AS 3, 4, 5, 8 (cont'd)

6.3 Unit Inlet Air (cont'd)

6.0 Mechanical

(cont'd)

WARNING

Disconnect the power before servicing the cooling module. Failure to

do so can cause electrical shock, personal injury or death.

Troubleshooting

Evap Cooler

Problem

Probable Cause

Remedy

Pump does not run.

Unit is calling for cooling

(control switch is in cooling

position) and reservoir is full.

1. Electrical connections

1. Verify all electrical connections. See Wiring Diagram.

2. Electric float switch on pump

2. Check position of the actuators on the electric float switch.

3. Dirty pump

3. Clean pump. See

FIGURE 22.

4. Defective pump

4. Replace pump.

Required water level (3")

not maintained (pump

and float control system)

1. Float valve

1. Adjust float valve. See Filling and Adjusting Water Level.

2. Optional drain and fill valves

2. Check valve for proper operation. See

FIGURE 16.

3. Incorrect overflow pipe nipple - should be 3-1/2"

3. Replace pipe nipple.

4. Drain leaking

4. Tighten drain plug.

Water running off of

media pads

1. Excessive water flow

1. See adjust water flow instructions.

2. Media needs cleaned or replaced.

2. Clean or replace media pads.

Water not distributing

evenly

1. Distribution line clogged

1. Flush distribution line. See Evap Cooling Module Maintenance.

2. Holes in distribution line turned

2. Check position of distribution line. Holes should be spraying

upward. If not positioned with holes up, adjust position of line.

3. Incorrect voltage to pump

3. Check voltage at pump terminal in cooling module junction box.

Media pads becoming

clogged & discolored

(scale/salt deposits) and/

or rapid deterioration of

the float switch

1. Bleed off line clogged or inadequate bleed off

(pump and float control system)

1. Clean bleed line (See

FIGURE 17). A uniform build-up of

minerals on the entering air face of the media indicates insufficient

bleed off. Increase the rate until the mineral deposits dissipate.

2. Excessive water flow

2. See Adjusting Water Flow.

Water blowoff from

media pads

1. Media pads installed incorrectly

1. Install media pads correctly. See Cooling Module Maintenance.

2. Requires moisture elimination pad (over 600 FPM) 2. Install moisture elimination pad. Consult factory.

3. Water level not 3 inches (pump and float control ) 3. See second problem listed above (Required water level)

6.4 Supply Air

Discharge

6.4.1. Duct

Connections

Requirements & Suggestions for Connecting and Installing Ducts

Type of Ductwork - The type of duct installation to be used depends in part on the

type of construction of the roof (whether wood joist, steelbar joist, steel truss, pre-

cast concrete) and the ceiling (whether hung, flush, etc.).

Ductwork Material - Rectangular duct should be constructed of not lighter than

No. 26 U.S. gauge galvanized iron or No. 24 B & S gauge aluminum.

Ductwork Structure - All duct sections 24 inches or wider, and over 48 inches

in length, should be cross broken on top and bottom and should have standing

seams or angle-iron braces. Joints should be S and drive strip, or locked.

Through Masonry Walls - No warm air duct should come in contact with masonry

walls. Insulate around all air duct through masonry walls with not less than 1/2" (1"

is recommended) of insulation.

Through Unheated Space - Insulate all exposed warm air ducts passing through

an unheated space with at least 1/2" (1" is recommended) of insulation.

Duct Supports - Suspend all ducts securely from adjacent buildings members. Do

not support ducts from unit duct connections.

System has either a horizontal or vertical discharge air opening with a duct flange.
If the discharge outlet is vertical, the system was ordered with either a factory-installed

downturn plenum (AQ Option).

Pump

Inside View of the

Junction Box

(Note: Only 208V

unit will have a

transformer in the

junction box.)

Float

Switch

Pump

Motor

To clean the pump, carefully

remove the mesh screening

(or basket) and the snap-on

cover plate.

FIGURE 22 - Remove

Junction Box, Pump

and Float Switch as an

Assembly
(

NOTE: Applies to

evaporative cooling

module with float and

pump control system

only. Depending on date

of manufacture, actual

assembly may not appear

exactly as in the photo.)