beautypg.com

0 maintenance and service, 1 maintenance schedule, 2 maintenance procedures – Reznor RPB Unit Installation Manual User Manual

Page 36: 1 maintenance schedule 10.2 maintenance procedures

background image

Form I-RPB, P/N 131782 R11, Page 36

WARNING

If you turn off the power supply, turn off the gas. See Hazard Levels,

page 2.

This unit will operate with a minimum of maintenance. To ensure long life and satis-

factory performance, a furnace that is operating under normal conditions should be

inspected every four months. If the furnace is operating in an area where an unusual

amount of dust or soot or other impurities are present in the air, more frequent inspec-

tion is recommended.
The following procedures should be carried out at least annually (See Paragraphs

10.2.1-10.2.4 for instructions).

Inspect the filters. Clean or replace as needed.

Inspect the blower and belt. Check belt for tension, wear and alignment. Adjust or

replace as needed. Clean dirt from blower and motor.

Clean all dirt and grease from the primary and secondary combustion air openings.

Check the gas valve to ensure that gas flow is being shut off completely.

Clean the heat exchanger both internally and externally.

Check the pilot burner and main burners for scale, dust, or lint accumulation.

Clean as needed.

Check the flue products outlet; clean if needed. Check the vent cap in an optional

extended vent system; replace any parts that do not appear sound.

Check the wiring for any damaged wire. Replace damaged wiring. (See Paragraph

7.0 for wiring requirements.)

CAUTION: When cleaning, wearing eye protection is recommended.

10.0 Maintenance

and Service

10.1 Maintenance

Schedule

10.2 Maintenance

Procedures

10.2.1 Gas Valve

WARNING

The operating valve is the prime safety shutoff. All gas supply lines

must be free of dirt or scale before connecting to the unit to ensure

positive closure. See Hazard Levels, page 2.

Remove external dirt accumulation and check wiring connections.

The combination gas valve must be checked annually to ensure that the valve is shut-

ting off gas flow completely.

Instructions:
1) Locate the 1/8” FPT INLET pressure tap on the combination valve (FIGURE 37).

NOTE: Use only factory-

authorized replacement

parts.

NOTE: Operational

pressure settings and

instructions for checking

pressure settings are in

Paragraph 6.1.

2) With the manual valve turned off to prevent flow to the gas valve, connect a

manometer to the 1/8” inlet pressure tap in the valve.

NOTE: A manometer (fluid-

filled gauge) with an inches water column scale is recommended.

3) With the field-installed manual valve remaining closed, observe the manometer

for two to three minutes for an indication of gas pressure. No pressure should

be indicated on the manometer.

If the manometer indicates a gas pressure,

the field-installed manual gas valve must be replaced or repaired before the

combination gas valve can be checked.

4) If the manometer does not indicate gas pressure, slowly open the field-installed

manual gas valve. After the manometer's indicated gas pressure has reached

equilibrium, close the manual shutoff valve. Observe the gas pressure. There

should be no loss of gas pressure on the manometer. If the manometer indicates

a loss of pressure, replace the combination gas valve before placing the heater in

operation.

CAUTION: DO NOT

bottom out the gas

valve regulator

adjusting screw.

This can result

in unregulated

manifold pressure

causing excess

overfire and heat

exchanger failure.

Single-

Stage Valve

1/8" INLET

Pressure Tap

1/8” Outlet

Pressure Tap

Two-Stage

Valve

1/8" INLET

Pressure Tap

1/8” Outlet

Pressure

Tap

FIGURE 37 - Top View of Gas Valves