3 mounting base and methods, 0 mounting (cont'd), 1 curb cap base – Reznor RPB Unit Installation Manual User Manual

Page 6: 3 mounting on a roof curb

background image

Form I-RPB, P/N 131782 R11, Page 6

5.3.1 Curb Cap Base

Outdoor systems are equipped with a load bearing curb cap which forms an integral

part of the unit. This curb cap has welded joints and has a "skirt" which fits over a roof

curb to provide a weatherproof installation. Four holes are provided at the curb cap

corners for lifting the unit. These holes do not interfere with unit weatherproofing. The

curb cap is not designed to be placed directly on the roof surface. The system

may be mounted on an optional roof curb purchased with the unit, a field-supplied roof

curb, or field-supplied supports. If the system has a downturn plenum and/or a bottom

return air opening, a roof curb is recommended to provide a weatherproof installation

as well as more workable clearances for ductwork.

5.3 Mounting Base

and Methods

5.3.2 Mounting

on Field-Supplied

Supports (without a

roof curb)

Prior to installation, be sure that the method of support is in agreement with all local

building codes and is suited to the climate. If considering this type of installation in

snow areas, it is recommended that the 4x4 wooden rails underneath the system be

on cross-support structure at least 12" higher than the roof surface (see support loca-

tions in

FIGURE 2B).

Whether the supports are being mounted directly on the roof or being placed "up" on

additional structure, the horizontal length of the system should be supported by two

4x4 treated wooden rails. Cut the rails to the appropriate length (Dimension "A") in

FIG-

URE 2A. (NOTE: Although dimensions are included for units with a downturn plenum

cabinet, it is strongly recommended that a full roof curb be used on an installation with

a downturn plenum cabinet and/or a bottom return air duct.)
Space the 4x4 wooden rails (See "B" Dimension,

FIGURE 2A) so that the curb cap

"skirt" will fit over the edge of the boards with the rails setting inside the horizontal

length of the curb cap.
If the rails are being laid directly on the roof, position them as shown in

FIGURE 2A.

Set the system on the rails, leaving the "ends" underneath open for ventilation.
If the treated wooden rails are not being placed directly on the roof surface, cross-

supports should be placed underneath the rails at the ends of the unit and at all cabinet

"joints" (between the blower cabinet and the furnace section and between the furnace

and the optional downturn plenum). See

FIGURE 2B.

The field-supplied, weather-resistant cross-support structure must be adequate for the

weight of the system. Cross-supports should run the entire width of the system sup-

porting the 4x4 wooden rails at the recommended locations (

FIGURE 2B).

Blower

Cabinet

Furnace

Section

Field

Supplied

Duct

4x4 Treated

Lumber

= Cross Support Locations

Field

Supplied

Duct

FIGURE 2B - Cross-Support Locations

Whether using an optional roof curb available with the system or a field-supplied curb,

the curb must be secure, square and level. The top surface of the roof curb must be

caulked with 1/4" x 1-1/4" sealant tape or two 1/4" beads of suitable sealant. The unit

must be sealed to the curb to prevent water leakage into the curb area due to wind

blown rain and capillary action. Except for the curb assembly details which are specific

to the optional roof curb available with the system, the information and requirements

FIGURE 2A - Mounting Support Dimensions (inches/mm)

A

B

4x4 Treated Lumber

Leave both

ends open

for ventilation.

Model

Series

RPB Size

Standard Heater

and Blower

Package

With Factory-Installed

Downturn Plenum

Cabinet (Option AQ)

All

"A"

"A"

"B"

125

60-5/8"

84-9/16"

24-5/16"

150, 175

60-5/8"

84-9/16"

29-13/16"

200, 225

60-5/8"

84-9/16"

35-5/16"

250, 300

60-5/8"

84-9/16"

43-9/16"

350

60-5/8"

84-9/16"

49-1/16"

400

60-5/8"

84-9/16"

54-1/2"

125

1540mm

2148mm

618mm

150, 175

1540mm

2148mm

757mm

200, 225

1540mm

2148mm

897mm

250, 300

1540mm

2148mm

1106mm

350

1540mm

2148mm

1246mm

400

1540mm

2148mm

1384mm

5.3.3 Mounting on a

Roof Curb

5.0 Mounting

(cont'd)