2 clearances, 0 mounting, 1 weights – Reznor RPB Unit Installation Manual User Manual

Page 5: 2 rigging and lifting, 1 weights 5.2 rigging and lifting

background image

Form I-RPB, P/N 131782 R12, Page 5

4.2 Clearances

REQUIRED CLEARANCES

Model

Series

Top

Sides

Bottom

Control

Opposite

To

Combustibles

To Non-

Combustibles

RPB

36"

(915mm)

Width of furnace

plus 6" (152mm)

6"

(152mm)

0 *

0

*

When installed on a roof

curb on a combustible

roof, the roof area

enclosed within the curb

must be either ventilated,

left open, or covered with

non-combustible material

which has an "R" value of

at least 5.0. See

FIGURE

3A, page 7.

86-11/16 (2202)

Blower

Cabinet

Furnace

Airflow

Field Control

Wiring

Entrance

39-3/16*

(995)

Optional Downturn Plenum Cabinet

A

38-1/8**

(968)

Field Wiring

(line voltage)

Gas

Curb

Cap

C

B

38-5/8 (981)

4-3/32

(104)

19-1/2

(495)

19-1/2

(495)

85-13/16 (2180)

Optional

Return

Air Inlet

Vertical

Discharge

1-1/32

(26)

4-1/4

(108)

4-1/4

(108)

Left Side View with Vertical Discharge

Front View with

Opt ional Vertical Discharge

(Downturn Plenum

Option AQ5 or AQ8)

4-3/32

(104)

5 (127)

19-1/2

(495)

4-5/8

(117)

31-11/32

(796)

43-17/32 (1106)

Screened

Outside

Air Hood -

Option AS2

5 (127)

19-1/2

(495)

Blower

Cabinet

1-1/32 (26)

61-3/8 (1559)

Control Wiring

Entrance

Furnace

Airflow

Curb

Cap

Gas

Field Wiring

(line voltage)

61-7/8 (1572)

A

38-1/8**

(968)

3/4(19)

3/4(19)

D

B

C

Left Side View with Horizontal Discharge

Front View with

Standard Horizontal Discharge

3/4(19)

3/4(19)

39-3/16*

(995)

18

(457)

11-1/4(286)

8-1/2(215)

NOTES:

*Height from top of

cabinet to top of curb

cap.
**Height from top of

cabinet to bottom of

cabinet side.

**** The two-position

discharge dampers in

Option AQ8 fit in the

discharge air opening.

The damper motor fits

inside the downturn

plenum cabinet.

Provide clearance to combustibles as shown in the table. Clearance to combustibles is

defined as the minimum distance from the heater to a surface or object that is neces-

sary to ensure that a surface temperature of 90°F above the surrounding ambient tem-

perature is not exceeded. Clearance is also required to sides of furnace for combustion

air space and for convenient installation and burner control system service.

5.0 Mounting

Approximate Net Weight (lbs/kg) - Model RPB Series Systems

(blower and furnace sections only)

Size

125

150, 175 200, 225 250, 300

350

400

Weight

lbs

482

520

534

588

630

662

kg

219

236

242

267

286

300

5.1 Weights

5.2 Rigging and

Lifting

Lifting holes are provided for rigging. Use spreader bars when lifting to prevent chains

or cables from damaging the unit. If the unit is being mounted on a roof curb, apply

caulking to the roof curb prior to lifting the unit and setting it on the curb. See

FIGURE

3A, page 7.

If the system includes an outside air hood, attach it after the unit is in place.