beautypg.com

0 mechanical (cont'd), 3 unit inlet air (cont'd), 3 optional dampers and controls – Reznor RPB Unit Installation Manual User Manual

Page 14

background image

Form I-RPB, P/N 131782 R11, Page 14

6.3 Unit Inlet Air (cont'd)

6.0 Mechanical

(cont'd)

6.3.3 Optional Dampers and Controls

(See Wiring Diagram on unit.)

NOTE: Damper controls are illustrated in

FIGURE 12A and 12B. These illustrations are intended to show location only of various air control accessories

and do not represent suggested combinations of accessories.

Furnace

Section

Blower

Blower Cabinet

30% Outside

Air Damper

30% Outside

Air Hood

Damper Motor

Return Air

FIGURE 12A - Location of Controls for

30% Outside Air Hood and Damper

Options (AR6 or AR7)

7

8

1

2

3 4 5 6

FIGURE 12B - Control

Locations for 100%

Outside Air and 100%

Return Air Damper

Options

1 Damper Motor

2 Return Air Damper

3 Potentiometer

4 Potentiometer

5 Mixed Air Controller

6 Warmup Control

7 Outside Air Damper

8 Damper Motor

Transformer

Damper Linkage - When units are equipped with

dampers, the dampers are closed during shipment. When

there are

both return air and outside air dampers, the

return damper linkage must be adjusted prior to use.
1. Loosen the set screw on the return air damper rod at

the damper arm.

2. Manually open the return air dampers. While the

dampers are opening, the damper rod and arm will

automatically move to their correct positions.

3. Tighten the set screw.

Outside Air

Damper

CLOSED

Return Air

Damper OPEN

Rod for Outside

Air Damper

Setscrew

Outside Air

Damper Arm

Return

Air

Damper

Arm

Rod for Return

Air Damper

Damper

Motor

FIGURE 12C - Example of Outside Air and Return Air

Damper Linkage

Pressure Null Switch

(Used to control

Outside Air Dampers in

Inlet Air Option AR23)

The pressure null switch used in Option AR23 is a Dwyer #1640-0 with a range of .01-

.20" w.c. It is shipped separately for field installation. Refer to the following paragraphs

and the manufacturer's installation instructions included with the switch.

Description and Application - The pressure null switch is a diaphragm operated dif-

ferential pressure switch used in makeup air applications to control building pressure.

It maintains a selected positive or negative pressure setpoint by changing the amount

of outside air being introduced to the building through the modulating outside air damp-

ers. As more pressure is required in the building, the pressure null switch activates the

damper motor driving the outside air damper towards the full open position and the

recirculated air damper towards the closed position. Conversely, as less pressure is

required, the switch drives the dampers in the opposite direction.
1. Select an indoor location free from excessive vibration where oil or water will not

drip onto the switch and where ambient temperature will be within a range of -30°F

(dry air) to 110°F.

2. Mount the switch with the diaphragm in a vertical plane. The switch is posi-

tion sensitive and is calibrated to operate properly when the diaphragm is vertical.

Mount switch securely.

3. Connect the pressure taps on the top of the switch to sources of air pressure differ-

ential. Metal tubing with 1/4" O.D. is recommended, but any tubing system which

will not unduly restrict the air flow may be used. To maintain a positive building

pressure, vent the low pressure tap to the outdoors and allow the high pressure

tap to monitor building pressure. To maintain a negative building pressure, reverse

the functions of the high and low pressure taps. In either case, be sure that the

outdoor vent is protected from the wind and screened from insects.

4. Adjustment of the Switch - The "HIGH" actuation point of the null switch is indi-

cated on a calibrated scale secured to the transparent range screw enclosure.

Installation Instructions

for Pressure Null

Switch (FIGURE 13)