beautypg.com

Reznor RPB Unit Installation Manual User Manual

Page 21

background image

Form I-RPB, P/N 131782 R12, Page 21

Duct Sizing - Proper sizing of the supply air ductwork is necessary to ensure a

satisfactory heating installation. The recognized authority for such information is

the Air Conditioning Contractors Association, 2800 Shirlington Road, Suite 300,

Arlington, VA 22206 (www.acca.org). A manual covering duct sizing in detail may

be purchased directly from them.

Furnace

Duct

“U” Channel

of Light

Gauge Metal

FIGURE 23B

- Install "U"

Channel on

Sides of Duct

Connection

Heater

Duct

Access Panel

in Duct

(152mm)

10” (254mm)

1

2

3

“U” Channel

(See FIGURE 9.)

FIGURE 23A - Connecting Supply Air Duct to the Furnace

(1) Flanges on the furnace (heat exchanger) turn out as shown. (2) Shape duct connection as shown - "U" on top

and bottom; "L" on sides.

(3) Slide "U" channels over furnace top and bottom flanges making connection.

Form "U" channels to seal sides.

Drill and lock with sheetmetal screws.

CAUTION: Joints where supply air ducts attach to the furnace must be sealed securely to prevent

air leakage into drafthood or burner rack area. Leakage can cause poor combustion, pilot problems,

shorten heat exchanger life and cause poor performance. See Hazard levels, page 2.

Bottom Duct/Furnace Connections - On outdoor models, insert ducts from

below roof deck through roof opening into the heater. Form 1" (25mm) flanges, fold

over, and fasten with sheetmetal screws inside heater. Gain access to the unit by

removing side panels from the blower and downturn plenum sections. Ducts must

be attached and sealed to provide airtight connections.

Return Air Duct/Furnace Connection - All return air ducts should be attached

and sealed to return air flanges to provide airtight connection.

Return Air Duct/Grill Size - Make certain that return air ducting or grills have a

free area equal to the return duct size connection.

CAUTION: An external duct system static pressure not within the limits shown on the rating plate,

or improper motor pulley or belt adjustment, may overload the motor. See Hazard Levels, page 2.

Removable Panels - The ducts should have removable access panels on

both upstream and downstream sides of the furnace. These openings must be

accessible when the furnace is in service and should be a minimum of 6" x 10"

in size so smoke or reflected light may be observed inside the casing to indicate

the presence of leaks in the heat exchanger. The covers for the openings must be

attached in such a manner as to prevent leakage. See

FIGURE 23A.

Supply Air Duct/Furnace Horizontal Connection - The seal between the furnace

and the duct must be mechanical. Duct connection should be made with "U" type

flanges on the top and bottom of the connecting duct. Slide the duct over the

flanges of the heater giving an airtight fit. Provide "U" type channels for the other

side flanges to ensure tight joints. Use sheetmetal screws to fasten ducts and "U"

channels to the furnace flange. See

FIGURES 23A and 23B.

6.4.2 Discharge Air

Sensor for Makeup

Air Application

Makeup air Option AG3 has a unit mounted ductstat with a capillary sensor that is

factory-installed in the unit discharge (See Paragraph 8.1.3).
Makeup air Options AG15, AG8, AG9, AG39, and AG40 require field installation of the

sensor in the discharge ductwork. Option AG15 uses the box and sensor holder in

FIGURE 23A. Options AG8, AG9, and AG39 include a sensor and mixing tube like the

one illustrated in

FIGURE 23B. Option AG40 requires a field-supplied sensor.

Follow the instructions below to install the sensor in the ductwork.
For control information, see Paragraph 8.1.