beautypg.com

5 electrical operating components, 0 electrical supply and connections (cont'd), 1 fan control – Reznor RPB Unit Installation Manual User Manual

Page 28: 2 reverse flow limit control

background image

Form I-RPB, P/N 131782 R11, Page 28

1. A fan control provides for the following control of the blower.

(a) After the gas valve opens, there is a time delay of blower operation to prevent

the discharge of cold air.

(b) Blower operation continues after the thermostat is satisfied as determined by

the fan time delay.

2. To be sure that the blower can continue to operate, the power supply to the

furnace

MUST NOT be interrupted except when servicing the unit.

3. If the customer wants the furnace off at night, the gas valve circuit SHOULD

BE OPENED by a single pole switch wired in series with the thermostat. Some

thermostats are provided with this feature. Multiple units controlled from a single

thermostat are shut off in the same manner. For proper operation, be sure the fan

control wiring is observed. For location, see

FIGURE 29, Item 12.

7.5.1 Fan Control

Service NOTE: To replace

the fan control on units

manufactured prior to

11/04, a replacement kit is

required. Order

P/N 209184.

7.5.2 Reverse Flow

Limit Control

These outdoor furnaces are factory equipped with an automatic reset reverse flow

limit control. This control is located in the blower compartment, mounted in the blower

junction box adjacent to the blower inlet opening, and is wired in series with the main

limit control mounted on the heat exchanger duct side. For location, see

FIGURE 29,

Item 32.

In case of belt breakage or motor failure, the limit control will be opened by the high

temperatures caused by reverse flow from the heat exchanger to the blower com-

partment, thus breaking the circuit to the automatic electric gas valve and preventing

burner operation.

7.0 Electrical Supply and Connections (cont'd)

27

30 31 32 33 34 35 36 37 38 39 40

26

29 25 28 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8

7

Optional

Downturn

Plenum

(Option AQ)

41 1

2

3

4

5

6

FIGURE 29 - Location of Standard and Optional Controls

1. Opt Auto Reset Discharge

Temperature Low Limit

2. Combustion Air Pressure

Switch

3. Opt Discharge Air Firestat

4. Ignition Controller

5. Optional Maxitrol Discharge

Air Sensor (Opt AG8 or 9)

6. Optional Two-Stage Controller

(Opt AG3) or Maxitrol Amplifier

(Opt AG7, 8, or 9)

7. Optional Main Low Gas Pres-

sure Switch

8. Optional Pilot High Gas Pres-

sure Switch

9. Optional Main High Gas Pres-

sure Switch

10. Time Delay Relay

11. Limit Control

12. Fan Control

13. Optional Discharge Tem-

perature Low Limit Time Delay

Relay

14. Line Voltage Terminal Block

15. Low Voltage Terminal Block

16. Discharge Temperature Low

Limit Relay

17. Optional Dirty Filter Pressure

Switch

18. Line Voltage Connection (field)

19. Optional Convenience Outlet

20. Blower Motor Contactor or

Starter

21. Optional High Ambient Limit

Control

22. Optional Outside Air or Return

Air Controller

23. Optional Mixed Air Controller

24. Optional Potentiometer

25. Optional Return Air Dampers

26. Optional Two Position or

Modulating Damper Motor

27. Optional Outside Air Damper

28. Optional Potentiometer

29. Optional Filters

30. Blower Motor

31. Optional Control Relays (as

required, 8 maximum)

32. Auto Reset Reverse Flow Limit

33. Optional Return Air Firestat

34. Low Voltage Terminal Strip

35. Line Voltage Terminal Strip

36. Control Transformer

37. Control Transformer (as

required)

38. Optional Damper Motor

Transformer

39. Low Voltage Connection (field)

40. Optional Air Proving switch

41. Venter Assembly

7.5 Electrical Operating Components