0 controls (cont'd), 1 gas controls (cont'd), Wiring and service - ag39 and ag40 – Reznor RPB Unit Installation Manual User Manual

Page 32: 5 optional electronic modulation (cont'd), Sensor location

background image

Form I-RPB, P/N 131782 R11, Page 32

Sizes with AG39&40 Startup Cold

Equilibrium at Full Rate

Factory Setting

125-225

-1.3" w.c.±0.2

-1.05" w.c.±0.1

-0.58" w.c.±0.05

250-400

-1.2" w.c.±0.2

-0.95" w.c.±0.1

-0.58" w.c.±0.05

Wiring and Service -

AG39 and AG40

For wiring, consult the wiring diagram attached to the furnace. All wires in the electrical

box connecting the modulation controls must have a temperature rating of 150°C.

This is a unique system which includes custom-built components and custom settings.

If service is required, follow the general troubleshooting guide on page 38 and the

special troubleshooting guide below.

Computer Controlled

Electronic Modulation

between 20-28%,

Option AG40

natural gas Model RPB

only; not available on

Size 350

With this option the furnace is equipped with a Maxitrol signal conditioner (See

FIG-

URE 32A) which accepts an input signal of either 4-20 milliamps or 0-10 volts from a

customer-supplied control device such as a computer. With the dip switches on the

conditioner in the "on" positions, the conditioner accepts a 4-20 milliamp signal. In

the "off" positions, the conditioner accepts a 0-10V signal. The conditioner converts

the signal to the 0 to 20 volt DC current required to control the modulating valve. The

heater functions and is equipped in the same way as for Option AG39 except that with

computer control the temperatures are selected through the field-supplied software

and there is no temperature selector or duct sensor.

reducing airflow through the burner. Safety switches monitor the position of the bypass

damper. When the gas pressure increases above 1.1" w.c., the bypass damper closes.

Combustion Air Pressure Switch Setting with AG39 and AG40

This uniquely designed modulation system requires combustion air pressure settings

different from the standard system. The approximate settings for the combustion air

proving switch at sea-level operation are:

Sensor Location

The duct temperature sensor and mixing tube are shipped loose for field installation in

the dicharge duct. See Paragraph 6.4.2 for instructions on locating the sensor in the

ductwork.
The sensor for Opiton AG40 is field suppleid. Follow the guidelines in Paragraph 6.4.2

and the manufacturer's instrucitons.

Troubleshooting Guides for

Checking Bypass Combustion

Air Damper Safety Circuit on

Model RPB with Option AG39

or Option AG40

Is there 24 volts

between Terminal 2 on #1

Time Delay Relay and

Terminal 7?

Go to

Troubleshooting

Chart for heater.

Is there 24 volts

between Terminal 84 and

Terminal 7?

Is the

damper open?

Is there voltage

between Terminal 88 and

Terminal 7?

Is there voltage

between Terminal 4 on

ignition permissive relay and

Terminal 7?

Replace #1 time delay relay.

Replace ignition

permissive

relay.

Check combustion

damper lower end switch

adjustment. If necessary,

replace end switch.

Is there voltage

between Terminal 87 and

Terminal 7?

Check combustion

damper lower end switch

adjustment. Replace end

switch if necessary.

Place a jumper across

Terminal 86 and Terminal 7.

Did the

damper close?

Replace motor run

time delay relay.

Replace combustion

damper gear motor.

Replace primary

manifold

pressure switch.

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

NO

YES

YES

NO

General Instructions: For each

step, check to ensure that the

wiring is not defective and that the

wiring connections are secure.

Symptom - Part 1:
Main burners are inoperative.
Assumes that 24 volts is

available between Terminal 2

and Terminal 7.

Symptom - Part 2:
Steady call for heat -

burner cycles.
Assumes constant

voltage between

Terminals 11 and 7 and

Terminals 2 and 7.

Measure manifold

pressure

during burner cycling.

When the

manifold pressure is

BELOW 1.0" w.c., is there a steady

voltage between Terminal 95

and Terminal 7?

Replace secondary

manifold pressure

switch.

While the

burner is cycling, is

there a steady voltage

between Terminal 84 and

Terminal 2?

Replace the primary manifold pressure switch.

When the

manifold pressure is

ABOVE 1.5" w.c., is there a steady

voltage between Terminal 95

and Terminal 7?

Replace secondary

manifold pressure

switch.

Is there voltage

between Terminal 4 of the

ignition premissive relay and

Terminal 7?

Replace ignition permissive relay.

YES

NO

YES

NO

YES

NO

8.0 Controls

(cont'd)

8.1 Gas Controls

(cont'd)

8.1.5 Optional Electronic Modulation (cont'd)