beautypg.com

Instructions – Reznor UEAS Unit Installation Manual User Manual

Page 9

background image

FIGURE 5 - Gas

connection is at the

pipe nipple that extends

outside the cabinet
Illustration shows

both a vertical and

horizontal gas supply;

requirements are the

same.

From Gas Supply

(horizontal or vertical)

Manual shutoff

Pipe nipple extending

outside the cabinet.

Drip

Leg

To Gas Valve

(inside the

cabinet)

To Gas Valve

(inside the

cabinet)

Ground

Joint

Union

Drip

Leg

Ground

Joint Union

Manual shutoff

WARNING

All components of a gas supply system must be leak tested prior to placing

equipment in service. NEVER TEST FOR LEAKS WITH AN OPEN FLAME. Failure to

comply could result in personal injury, property damage or death.

7.1.3 Valve Outlet or

Orifice Pressure Setting

Measuring valve outlet gas pressure cannot be done until the heater is in opera-

tion. It is included in the steps of the “Check-Test-Start” procedure in Paragraph

11. The following warnings and instructions apply.

WARNING

Valve outlet gas pressure must never exceed 3.5” w.c.

for natural gas and 10” w.c. for propane gas.

For Natural Gas: When the heater leaves the factory, the combination

gas valve is set so that the valve outlet gas pressure for a single-stage

valve is regulated to 3.5” w.c. Inlet supply pressure to the valve for natural

gas must be a minimum of 5” w.c. or as noted on the rating plate and a

maximum of 14” w.c.

For Propane: The heater is shipped factory equipped for use with natural gas. A

propane conversion kit is included. Follow the instructions in Paragraph 7.1.4 to

convert for use with propane.
At startup, measure the valve outlet pressure. Refer to the pressure chart on page

10 for correct outlet pressure.
When using propane, the inlet supply pressure to the valve must be a minimum of

11” w.c. and a maximum of 14” w.c.
Before attempting to measure or adjust valve outlet gas pressure, the inlet supply

pressure must be within the specified range both when the heater is in operation

and on standby. Incorrect inlet pressure could cause excessive valve outlet gas

pressure immediately or at some future time. If natural gas supply pressure is too

high, install a regulator in the supply line before it reaches the heater. If natural gas

supply pressure is too low, contact your gas supplier.

NOTE: A gas conversion kit for

changing from natural gas to

propane is included with each

heater. See Paragraph 7.1.4 for

conversion instructions.

Check Valve Outlet

Pressure (can only be

done after heater is

operating)

NOTE: If operating at high

altitude, outlet pressure requires

adjustment. Follow instructions

below.

Instructions

1) Locate the 1/8” output pressure tap on the valve (See FIGURE 6, page 10).

With the manual valve turned off to prevent flow to the gas valve, connect

a manometer to the 1/8” pipe outlet pressure tap in the valve.

NOTE: A

manometer (fluid-filled gauge) is recommended rather than a spring type

gauge due to the difficulty of maintaining calibration of a spring type gauge.

2) Open the manual valve and operate the heater. Depress and hold the door

safety switch. Cycle the burner once or twice to properly seat the adjustment

spring in the valve. Measure the outlet pressure of the gas valve.

Form I-UEAS, P/N 221232 R13, Page 9