beautypg.com

Reznor UEAS Unit Installation Manual User Manual

Page 23

background image

FIGURE 17 - Concentric

Adapter, Outdoor

Combustion Air Pipe,

and Concentric Vent

Pipe

Concentric

Adapter Box

X = length of combustion

air pipe required through

and above the roof. Height

from box to top of inlet

air pipe must not

exceed 48” (1219mm).

Minimum height above

the roof is 18” (457mm)

and must be higher than

anticipated snow depth.

FIRST,
1)
Determine length (X) of
combustion air pipe (see
requirements on the left).
2) Attach the 8” combustion air
pipe to the collar on the box.
3) Inside, use field-supplied
hardware to attach the box
to the roof.

V

ent Flow

23” (584mm) minimum

Cold Climate NOTE:

In geographic areas where

the design ambient is -10°F

or lower, this minimum

height is 34” (864mm).

Collar for attaching

indoor 6” diameter

Combustion Air Pipe

SECOND,

Extend one

continuous

piece of

vent pipe

through the

attached box,

through the

combustion

air pipe, and

the required

height above

the combustion

air pipe.

Silicone Ring

12” (305mm) minimum -

6” (152mm) through the

box plus enough length

below to attach to coupler

Outside view with concentric
adapter box attached to
underside of roof. Install
field-supplied flashing at
roof opening.

Snow Clearance

18” (457mm)

minimum

(NOTE: Maximum

from concentric

adapter box is

48” (1219mm).

FIGURE 18 - Outside

View of Combustion Air

Pipe with Box Attached

to Under Side of Roof

6. Determine the length and install the “terminal end” vent pipe.

6a) Refer to FIGURE 17 and determine the required length of the continuous sec-

tion of vent pipe. The length of the vent pipe extending through the box, through

the combustion air inlet pipe, and the height required above the combustion air

inlet air pipe must be one piece of pipe without joints.
Determine the length by adding the requirements:

Starting with at least 6” (152mm) below the box for attaching to the coupler;
plus 6” (152mm) through the concentric adapter box;
plus the length of the combustion air pipe;
plus a minimum of 23” (584mm) beyond the top of the combustion air pipe.
Total is the

minimum length of the vent pipe section.

NOTE: A longer vent pipe may be required; see FIGURE 17.

6b) Install the “terminal end” vent pipe.

Being sure the pipe is in the proper flow direction, slide the end into the box and

out through the combustion air pipe. Position the pipe so that it extends beyond

the combustion air pipe the height determined in

6a) above. Verify that the silicone

ring is seated properly.
Join the terminal vent pipe to the vent pipe run. Re-check the silicone ring to be

sure that it is still properly seated.

Form I-UEAS, P/N 221232 R13, Page 23