beautypg.com

3 troubleshooting, 0 maintenance and service (cont’d), 2 maintenance procedures (cont’d) – Reznor UEAS Unit Installation Manual User Manual

Page 40

background image

12.2 Maintenance Procedures (cont’d)

For location of controls,

see FIGURE 28, page 37.

12.2.12 Vent Temperature Limit Switch

The vent temperature limit switch is located on the discharge of the combustion

air blower (venter) and its purpose is to prevent the vent gas temperature from

exceeding a temperature that will harm the PVC vent pipe. If the vent temperature

limit switch is activated, the cause must be determined and corrected before the

heater is placed back into operation. Activation of the manually reset vent tempera-

ture limit switch could be caused by one or more of the following:

Manifold gas pressure too high

The heat content of the fuel being burned is too high

Reduced circulating airflow due to dirty an/or plugged air moving

components

Excess dirt on the heat exchangers

Failed heat exchanger(s)

After the cause is determined and corrected, depress the red button on the switch

to reset it.

12.2.13 Disconnect Switch

The disconnect switch is located in the sealed electrical box inside the control

compartment with the toggle on the rear of the heater.
If it is determined that the disconnect switch needs replacing, use only the factory-

authorized replacement part that is designed for the heater. Always replace electri-

cal box cover.

Disconnect

Switch

Vent Temperature

Limit Switch

12.2.14 Vent/Combustion

Air System

Check the complete system at least once a year. Inspection should include all

joints, seams, concentric adapter box, inlet air guard or cap, and the vent terminal

cap. Clean openings. Replace any defective parts.

12.2.15 Condensate

Drain System

Check the condensate disposal system annually. Remove the condensate traps

and flush them with clear tap water to remove any sediment that my have accumu-

lated. Check to be certain the piping to the sanitary drain has not been damaged.

Check the sanitary drain to verify that it flows freely.

12.0 Maintenance

and Service

(cont’d)

12.3 Troubleshooting

The integrated circuit board monitors the operation of the heater and includes two

LED signal lights that indicate normal operation and various abnormal conditions.

If the heater fails to operate properly, check this signal to determine the cause

and/or to eliminate certain causes. LED is visible through the door. See operating

sequence in Paragraph 10.
Do not attempt to repair the DSI integrated control module (circuit board); the only

field replaceable component is the fuse.

Check the Lights on the DSI Integrated Control Module (Circuit

Board)

IMPORTANT: When using

a multimeter to troubleshoot

the 24 volt circuit, place the

meter’s test leads into the 5 or

9 pin connectors located on the

ignition control. Do not remove

connectors or terminals from the

electrical components. Doing

so can result in misinterpreted

readings due to the ignition

control board’s fault mode

monitoring circuits.

Control Status - Green LED Codes

Steady ON.....Normal Operation, No call for heat

Fast Flash......Normal Operation, Call for heat

1 Flash...........System Lockout, Failed to detect or sustain flame

2 Flashes.......Pressure Switch Did Not Close within 30 Seconds of Venter Motor

3 Flashes.......High Limit or Vent Temperature Limit Open

4 Flashes.......Pressure Switch is Closed Before Venter Motor is Energized

Steady OFF....Blown fuse, No Power, or Defective Board

Flame Status - Yellow LED Codes

Steady ON.....Flame is sensed

Slow Flash.....Weak flame (current below 1.0 microamps ± 50%)

Fast Flash.....Undesired Flame (valve open and no call for heat)

Form I-UEAS, Page 40