beautypg.com

0 controls -30, 1 thermostat 9.2 gas valve 9.3 safety controls, 0 controls – Reznor UEAS Unit Installation Manual User Manual

Page 29: 2 gas valve 9.3 safety controls, 1 thermostat, Danger

background image

9.0 Controls

The main operating gas valve is powered by the 24-volt control circuit through the

thermostat and safety controls. The main control valve is a diaphragm type providing

regulated gas flow preset at the factory. (For location, see

FIGURE 28, page 37.)

9.2 Gas Valve

9.3 Safety Controls

9.3.1 Combustion Air Proving (Pressure Switch)

The combustion air proving switch is a pressure sensitive switch that monitors air

pressure to ensure that proper combustion airflow is available. The switch senses

the differential pressure between the negative pressure in the venter housing and

the pressure in the cabinet. (For switch location, see

FIGURE 28, page 37.)

On startup when the heater is cold, the sensing pressure is at the most negative

level, and as the heater and vent system warm up, the sensing pressure becomes

less negative. After the system has reached equilibrium (about 20 minutes), the

sensing pressure levels off.
If a restriction or excessive vent length or turns cause the sensing pressure to be

outside the switch setpoint, the pressure switch will function to shutoff the main

burner. The main burner will remain off until the system has cooled and/or the flue

system resistance is reduced.
The Table below lists the approximate water column differential pressure readings

and switch setpoints for sea level operating conditions for Model UEAS heaters.

9.1 Thermostat

If the thermostat has an anticipator setting, make sure it is set to 0.6 amps (or in

accordance with the amperage value noted on the wiring diagram of your heater).
Make thermostat connections at the terminal strip on the back of the heater. The

strip has four terminals, G, W1, R, and W2; refer to the wiring diagram.
IMPORTANT: All units MUST be operated by a 24-volt thermostat. Never use a

line voltage disconnect switch as a means of operating the heater.
Multiple Heater Control, Option CL31 and Option CL32

-

If the heater was

ordered with a multiple heater control option, one thermostat can be used to control

up to six heaters. The option includes a 40VA transformer that replaces the stan-

dard transformer in the “controlling” unit and a relay assembly that attaches to the

additional unit. Option CL31 provides for control of two heaters. If control of addi-

tional heaters is desired (up to six total), Option CL32 which is the relay assembly

only must be added to each additional heater.

The option packages are shipped separately and include complete instructions on

installation and wiring.

Pressure Switch

Identification

DANGER

Safe operation of this unit requires proper venting flow. NEVER bypass combustion air

proving switch or attempt to operate the unit without the venter running and the proper flow

in the vent system.Hazardous conditions could result. See Hazard Intensity Levels, page 2.

Model

UEAS

Startup

Cold

Equilibrium

Hot

Setpoint

OFF

Setpoint

ON

Label

Color

Altitude

(FT.)

Switch

P/N

Differential Pressure Measured in " w.c.

130

3.0

2.8

2.65

2.75

Yellow

0 to 6,000

221251

180

3.1

2.8

2.30

2.91

Blue

221228

260

3.3

2.9

310

3.5

3.2

130

2.95

2.75

2.60

2.65

Green

6,001 to

10,000

235954

180

3.05

2.75

2.25

2.30

Orange

235953

260

3.25

2.85

310

3.45

3.15

WARNING

The operating valve is the prime safety shutoff. All gas supply lines must be free

of dirt or scale before connecting the unit to ensure positive closure. See Hazard

Levels, page 2.

Form I-UEAS, P/N 221232 R13, Page 29