beautypg.com

2 clearances, 0 high altitude operation 6.0 hanging the heater – Reznor UEAS Unit Installation Manual User Manual

Page 7

background image

4.2 Clearances

Clearances

Model UEAS

130, 180, 260,

310

Top

Flue Connector

Access Panel

Non-Access Side

Bottom*

Rear**

inches

mm

inches

mm

inches

mm

inches

mm

inches

mm

inches

mm

4

102

6

152

18

457

2

51

1

25

18

457

*Suspend the heater so that the bottom is a minimum of 5 feet (1.5M) above the floor.

** Measure rear clearance from the fan motor.

Units must be installed so that the clearances in the table are provided for combus-

tion air space, inspection and service, and for proper spacing from combustible

construction. Clearance to combustibles is defined as the minimum distance from

the heater to a surface or object that is necessary to ensure that a surface temper-

ature of 90°F (50°C) above the surrounding ambient temperature is not exceeded.

If the heater is being installed at an elevation above 2000 ft (610M), the input rate

will have to be derated. This is done by adjusting the valve outlet pressure. Adjust-

ing the valve outlet pressure is done after the heater is in operation; follow the

instructions in Paragraph 7.1.3. Capacities and inputs for derated units are also

listed in Paragraph 7.1.3.

5.0 High Altitude

Operation

6.0 Hanging the

Heater

Before suspending the heater, check the supporting structure to be used to verify

that it has sufficient load-carrying capacity to support the weight of the unit.

Model

UEAS -

Weights

Size

130

180

260

310

lbs

230

245

360

395

kg

104

111

163

179

WARNING

Unit must be level

for proper operation.

Do not place or add

additional weight

to the suspended

heater. Hazard

Levels, page 2.

WARNING

Check the supporting structure to be used to verify

that it has sufficient load carrying capacity to support

the weight of the unit. Suspend the heater only from the

threaded nut retainers or with a manufacturer provided

kit. Do NOT suspend from the heater cabinet.

When the heater is lifted for suspension, support the bottom of the heater with plywood or other appropriately placed

material. If the bottom is not supported, damage could occur. Before hanging, verify that any screws used for holding

shipping brackets were re-installed in the cabinet.
The heater has four-point suspension. Suspension point dimensions are shown in

FIGURE 2, page 6. A 3/8”-16 threaded

nut retainer is located at each suspension point (

FIGURE 4A).

If ordered with swivel connectors, Option CK10, for 1” pipe attach the swivels at the threaded nut retainers. Suspend

with 1” pipes (

FIGURE 4B).

FIGURE 4B - Swivel Connectors,

Option CK10, to Suspend the Heater

from 1” Pipes

Lock the swivel

connector to

the heater.

The connector

is threaded for

hanging from

a 1” pipe.

Add a 3/8” nut

and washer to

lock the hanger

rod to the heater.

3/8” threaded rod

(field supplied)

Be sure the threaded swivel

connectors are locked to the

heater as illustrated.

Be sure the threaded hanger rods are locked to

the heater as illustrated. Length of threaded rod

extending into the heater MUST NOT exceed 1/2”

(13mm).

Recommended maximum hanger rod length is 6

feet (1.8M).

FIGURE 4A - Suspending

the Heater with Rods

from the Threaded Nut

Retainers

Form I-UEAS, P/N 221232 R13, Page 7