beautypg.com

2 venting and combustion air, 0 mechanical (cont’d), 1 gas piping and pressure (cont’d) – Reznor UEAS Unit Installation Manual User Manual

Page 12

background image

7.1 Gas Piping and

Pressure (cont’d)

7.1.4 Converting from Natural Gas to Propane (cont’d)

7.2 Venting and

Combustion Air

All separated combustion units MUST BE equipped with both combustion air and

exhaust piping to the outdoors. The unique concentric adapter box required with

this heater allows for both combustion air and exhaust piping with only one hori-
zontal or vertical penetration hole in the building.
Concentric horizontal and vertical vent/combustion air systems (Option CC6 or

Option CC2) are the only venting/combustion air systems approved for high effi-

ciency Model UEAS separated-combustion unit heaters.
Model UEAS units are certified as Category IV heaters. These heaters are very

thermal efficient and will produce condensate during operation. The heater and

its venting system must be connected to a drain. See Paragraph 7.3, page 25, for

instructions on installing the condensate drain.

7.2.1.1 Types of Pipe

Provide field-supplied pipe in the types listed.
Vent Pipe - Schedule 40 PVC or CPVC pipe. In Canada, all PVC vent pipe must

be approved to ULC 636.
Combustion Air Inlet Pipe - Sealed, single-wall galvanized pipe is recommended

for the combustion air pipe.

7.2.1 Vent/Combustion

Air System

Requirements

7.0 Mechanical

(cont’d)

FIGURE 7 - Rear of a

Model UEAS Heater

showing the Locations

of Both Inlet Air

and Venter Outlet

Connections

Line Voltage Entrance

Gas Connection

(External)

6” dia Collar for

Combustion Air Pipe

Condensate Drain (1/2” PVC pipe)

4” PVC Vent Pipe (See vent conden-

sate drain requirements in FIGURE

8A, 8B, 9A ,or 9B and PVC joint

requirements in Paragraph 7.2.1.6.)

24V Terminal Strip

3-1/4” (83mm)

8-1/4” (210mm)

Sizes 130, 180; 4-5/16”(110mm)

Sizes 260, 310; 5-1/16”(129mm)

Sizes 130, 180;

8-5/16”(211mm)

Sizes 260, 310;

9-3/32”(231mm)

Rear View of Model UEAS

Disconnect Switch

7.2.1.2 Venter Outlet and

Combustion Air Inlet

7.2.1.3 Vent Condensate

Drain Connection

A condensate drain is required in the vent pipe. See

FIGURES 8A and 8B for

vertical vent or

FIGURES 9A and 9B for horizontal vent run with either horizon-

tal or vertical vent. For Canadian installation, refer to

FIGURE 8B or 9B only. In

Canada, all PVC vent pipe must be approved to ULC S636.
The 4” PVC cap with drain connection opening shown in

FIGURES 8A and 9A

is supplied with every heater. The drain connection, drain piping, and 4x4x4 PVC

vent pipe tee are field supplied. All of the vent and drain components shown in

FIGURES 8B and 9B are field supplied.

4. Fill in the information required on the gas conversion tape. Select a location

near the rating plate. Be sure the surface is clean and dry and affix the

conversion tape and propane label to the heater.

5. During heater startup, follow the instructions in Paragraph 7.1.3 to check the

valve outlet pressure.

Form I-UEAS, Page 12