beautypg.com

0 maintenance and service (cont’d), 2 maintenance procedures (cont’d) – Reznor UEAS Unit Installation Manual User Manual

Page 38

background image

Ignitor - Refer to FIGURE 28 and locate the ignitor. Disconnect the wire; remove

the screw and the ignitor. Clean the ignitor assembly with an emery cloth.
Spark gap must be maintained to 1/8”. See

FIGURE 30.

IMPORTANT: When re-assembling, the brown ground wire must remain attached

to the ignitor.

CAUTION: Due to high voltage on the spark wire and electrode,

do not touch when energized. See Hazard Levels, page 2.

Ignitor

1/8 inch

(3.2mm)

Flame Sensor - Refer to FIGURE 28 and locate the

flame sensor. Disconnect the wire; remove the screw

and the flame sensor. Clean with an emery cloth.

Flame Sensor

12.2.5 Fan Motor, Fan

Blades, and Guard

Remove dirt and grease from the motor, the fan guard, and blades. Use care when

cleaning the fan blades to prevent causing misalignment or imbalance. Check that

the hub of the fan blades is secure to the shaft.
Follow these instructions for replacement of the fan guard, fan motor and/or fan

blades.

1. If the heater is installed, turn off the gas and disconnect the electric power.
2. Open the access door and disconnect the fan motor wires, capacitor wires at

the capacitor, and ground screw.

3. Remove the assembled parts (the fan guard, the motor and the fan blade).
4. Disassemble and replace whatever parts are needed and reassemble using

whatever part(s) are being replaced and the original parts.

Be sure the fan blade is in the proper position on the shaft; refer to the illustra-

tion and table in

FIGURE 31.

Position the assembly on the heater. Attach the fan guard.
Rotate the fan blade to check for adequate clearance. If adjustment is

required, loosen the mounting screws, re-position the fan guard, and tighten

the screws. Rotate the fan blade and re-check for adequate clearance.

Repeat this procedure until the assembly is positioned properly.

5. Reconnect the fan motor wires according to the wiring diagram and close the

access panel.

6. Restore power to the heater and turn on the gas. Light, following the instruc-

tions on the lighting instruction plate. Check for proper operation.

12.2.6 Venter Motor, Wheel, and Pressure Sensing Tap

Remove dirt and grease from the motor casing, the venter housing, pressure

sensing tap, and the venter wheel. Venter motor bearings are permanently lubri-

cated. Follow these instructions for replacement of the venter motor and wheel

assembly. Keep all hardware removed to be used in re-assembling and installing

the replacement parts.

12.2 Maintenance

Procedures

(cont’d)

FIGURE 30 - Ignitor showing required Spark

Gap Measurement

Dimension A

Size

inches

mm

130, 180

1-5/8

67

260

2

51

310

1-7/8

48

A

Fan

Motor

Fan

Blade

FIGURE 31 - Fan Blade

Position on the Shaft

12.0 Maintenance

and Service

(cont’d)

1. Turn off the gas and disconnect the electric power.
2. Open the burner/control compartment access panel.

Replacement

Instructions

Do not attempt to disassemble the control module. However, each heating season

check the lead wires for insulation deterioration and good connections.
Proper operation of the direct spark ignition system requires a minimum flame

signal of 1.0 microamps as measured by a microampmeter.
NOTE: For additional information and check out procedure on the direct spark

ignition system, refer to Paragraph 10 and the Troubleshooting Flow Chart in

Paragraph 12.3.

12.2.4. Ignition System (cont’d)

Form I-UEAS, Page 38