beautypg.com

Combustion air pressure switch, Limit control, Warning – Reznor UEAS Unit Installation Manual User Manual

Page 39

background image

FIGURE 32 - Venter Wheel

Position on Shaft

1/2” (13mm) from

motor plate to wheel

Venter

Motor

Venter Wheel

Motor Plate with Gasket

WARNING

The operating valve

is the prime safety

shutoff. To ensure

positive closure, clean

all dirt and scale from

gas supply lines before

connecting to the unit.

See Hazard Levels,

page 2.

12.2.7 Operating Gas

Valve

NOTE: Operational pressure

settings and instructions for

checking pressure settings are

in Paragraph 7.1.3.

FIGURE 33 - Pressure

Tap for Checking Gas

Flow Shutoff

1/8” Outlet

Pressure Tap

Top Views of Two Styles of

Valves used on UEAS Units

Carefully remove external dirt accumulation and check wiring connections.
The combination gas valve must be checked annually to ensure that the valve is

shutting off gas flow completely.

Instructions:

1) Locate the 1/8” NPT pressure tap on the combination valve.
2) With the manual valve turned off to prevent flow to the gas valve, connect a

manometer to the 1/8” outlet pressure tap in the valve.

NOTE: A manometer

(fluid-filled gauge) is recommended.

3) Turn the manual valve to the ON position and the heater OFF. Use your

finger to fully block the main burner orifice for several seconds. Observe the

manometer with the orifice blocked, and if any pressure is indicated, the gas

valve is leaking.

A leaking gas valve must be replaced before the heater is

put back in operation

1/8”

Outlet

Pressure

Tap

12.2.8

Combustion Air Pressure Switch

See

FIGURE 28, page 37, for location. If it is determined that the pressure switch

needs replacing, use only the factory-authorized replacement part that is designed

for the model and size of heater being serviced.

Pressure

Switch

12.2.9

Limit Control

If it is determined that the limit control needs replacing, use only a factory-autho-

rized replacement part that is designed for the size of heater.
For approximate limit location, see

FIGURE 28, page 37.

Limit

Control

3. Disconnect the three venter motor wires at the DSI control, capacitor

wires at the capacitor (if applicable), and ground screw (located on the

control panel).

4. Holding the venter motor, remove the six screws that attach the venter

motor mounting plate to the venter housing. Remove the motor and

wheel assembly from the heater.

5. Re-assemble with the replacement venter motor and wheel assem-

bly. See

FIGURE 32. If the motor plate gasket is damaged, it must be

replaced.

6. Follow the wiring diagram to connect the venter wires.
7. Replace the access panel. Restore power to the heater and turn on the

gas. Light, following the instructions on the lighting instruction plate.

Check for proper operation.

12.2.10 Door Switch

If it is determined that the door switch needs replacing, use only a factory-autho-

rized replacement part that is designed for the heater.

Door

Switch

Transformer

12.2.11 Transformer

Use a voltmeter to verify that there are 24 volts output from the transformer.

If the transformer is not functioning, it must be replaced. Use a replacement

transformer identical to the factory-installed model.

Form I-UEAS, P/N 221232 R13, Page 39