beautypg.com

0 mechanical (cont’d), 2 venting and combustion air (cont’d), 2 horizontal vent terminal installation (cont’d) – Reznor UEAS Unit Installation Manual User Manual

Page 20

background image

FIGURE 16 - Typical Installation of a Model UEAS High Efficiency, Separated-Combustion

Unit with a Horizontal Vent/Combustion Air Terminal (Option CC6)

Wall

Insert the Bird

Screen into the

socket of

the elbow.

Inlet Air

Guard

6” dia Single-Wall Metal Combustion

Air Pipe to Heater (seal joints)

4” dia CPVC or PVC Vent

Pipe Run from the Heater

Heater

Minimum distance between the

Concentric Adapter Box

and the Heater is 3 ft (9M).

Use the brackets on sides of box and field-supplied

hardware to attach the box to the inside wall.

One-piece, 4” dia,

Schedule 40 PVC

or CPVC Vent Pipe

Minimum

4” (102mm)

Maximum

16” (406mm)

1” (25mm

)

Minimum

48” (1219mm

)

Maximum

Minimum

3” (76mm)

Maximum

6” (152mm)

Pitch vent pipe toward the heater

1/4” per foot for condensate drain.

6” (152mm

)

Box Wid

th

*

Attach a 22.5°

Elbow to the end

of the vent pipe

with a sheetmetal

screw.

* A 90° or 45° elbow may be used

in place of the 22.5° elbow.

Top View

Use the brackets on

the sides of the box

and field-supplied

hardware to secure

the Concentric Adapter

Box to the inside wall.

Y

Minimum**

3 ft (1M)

Minimum

X - Minimum**

Adjoining Building

Building Projection

Building Overhang

[NOTE: Maximum overhang

is 24” (610mm).]

Wall

Rain water should drain out the

hole drilled in the bottom of the

pipe and/or the end of the pipe.

When sealing and/or flashing

around the combustion air pipe,

adjust so that the pipe has a slight

downward slope to prevent rain

water from running into the

concentric adapter box.

Flashing/

Sealing

(see right

below)

* 22.5° PVC Elbow

(attached at the

top with a

sheetmetal screw)

* A 90° or 45° elbow may be used in

place of the 22.5° elbow.

Side View

UEAS

Sizes

X

Y

130, 180 8 ft 2.4 M 36" 914 mm
260, 310 10 ft 3.0 M 48" 1219 mm

**Minimum - Check for and comply

with local Codes.

5. Attach the concentric adapter box to the wall.

Insert the combustion air pipe with inlet guard attached out through the wall.

Position the box so that the pipe is centered in the opening. Attach the brackets

to the wall with field-supplied hardware.
6. Determine length and install the “terminal-end” vent pipe.

6a) Determine length of pipe. The length of the continuous piece of terminal-

end vent pipe is determined by the installation within the maximum and minimum

requirements. See

FIGURE 16 to determine lengths of each segment and

calculate the total length required. The “terminal-end” vent pipe extending

through the box and concentric through the inlet air pipe must be one piece of

vent pipe without joints.

7.2.2 HORIZONTAL VENT TERMINAL Installation (cont’d)

7.2 Venting and Combustion Air (cont’d)

7.0 Mechanical

(cont’d)

Form I-UEAS, Page 20