beautypg.com

Cotinued) – Reznor UEAS Unit Installation Manual User Manual

Page 41

background image

Trial for Ignition

Call for Heat

Is there a

spark across gap at

ignitor?

Does gas

ignite?

Is there minimum

flame current at the

flame sensor?

Is there

minimum flame current

at the control

module?

Replace control

module.

Check connections to flame

sensor and/or moisture in the

burner assembly.

Is the flame

sensor corroded?

Clean flame

sensor.

Is the sensor

located in flame

correctly?

Replace flame

sesnsor.

Reposition

flame sensor.

Is gas

flowing?

Is the ignitor

position correct in the

gas flow?

Check gas pressure

and supply voltage.

If either are low,

correct and repeat

startup.

Reposition

spark ignitor.

Is there

24VAC at the gas

valve?

Is there 24VAC

from gas valve output on

control module to

chassis?

Check wiring and

connections to

gas valve.

Replace

ignition

control

module.

Replace gas

valve.

Is there

spark voltage at

control?

Check high

voltage wire

continuity.

Is there 24V P1-2

to power control?

Replace

control

module.

Check wiring

and/or 24VAC

transformer output.

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

NO

YES

YES

NO

YES

NO

YES

NO

DSI Integrated Control Module

(Circuit Board) Trial

Troubleshooting

Flowchart

General Troubleshooting

PROBLEM

PROBABLE CAUSE

REMEDY

Venter motor

will not start

1. No power to unit.

1. Turn on power; check supply fuses or main circuit breaker. Turn on built-in

disconnect switch; replace switch if not operating.

2. No 24V power to integrated circuit board. 2. Turn up thermostat; check control transformer output.

3. Integrated circuit board fuse blown.

3. Correct cause. Replace fuse (type ATC or ATO, 32VDC, 3A).

4. No power to venter motor.

4. Tighten connections at circuit board and/or motor terminals.

5. Integrated circuit board defective.

5. Replace integrated circuit board.

6. Defective venter motor.

6. Replace venter motor. See Paragraph 12.2.6.

Burner will not

light

1. Manual valve not open.

1. Open manual valve.

2. Air in the gas line.

2. Bleed gas line (initial startup only).

3. Gas pressure too high or too low.

3. Supply pressure should be 5-14" w.c. for natural gas or 11-14" w.c. for propane.

4. No Spark:

4.

a) Loose wire connections.

a) Be certain all wire connections are solid.

b) Transformer failure.

b) Be sure 24 volts is available.

c) Incorrect spark gap.

c) Maintain spark gap at 1/8" (3.2mm).

d) Spark cable shorted to ground.

d) Replace worn or grounded spark cable.

e) Spark electrode shorted to ground.

e) Replace if ceramic spark electrode is cracked or grounded.

f) Burner not grounded.

f) Make certain integrated circuit board is grounded to ignitor.

g) Circuit board not grounded.

g) Make certain integrated circuit board is grounded to furnace chassis.

h) Unit not properly grounded.

h) Make certain unit is properly field grounded to earth ground and properly

phased (L1 to hot lead L2 to neutral).

i) Integrated circuit board fuse blown.

i) Correct cause. Replace fuse (type ATC or ATO, 32VDC, 3A).

j) Faulty integrated circuit board.

j) If 24 volt is available to the integrated circuit board and all other causes have

been eliminated, replace board.

5. Lockout device interrupting control circuit

by above causes.

5. Reset lockout by interrupting control at the thermostat or main power.

6. Interlock door switch open.

6. Close access door or replace switch.

7. Combustion air proving switch not

closing

7.

a) Make sure unit is properly vented.
b) Remove obstructions from vent.

c) Replace faulty tubing to pressure switch.

8. Faulty combustion air proving switch.

8. Replace combustion air proving switch.

9. Main valve not operating.

9.

a) Defective valve.

a) If 24 volt is measured at the valve connections and valve remains closed,

replace valve.

b) Loose wire connections

b) Check and tighten all wiring connections.

(cotinued)

Form I-UEAS, P/N 221232 R13, Page 41