beautypg.com

Reznor UEAS Unit Installation Manual User Manual

Page 13

background image

Installer-provided

4x4x4 PVC Sweep

or Sanitary Tee

4” PVC Cap is included in the vent/

combustion air kit(OptionCC2). Cap

is drilled and tapped for field-supplied

1/2” NPT condensate drain.

Field-supplied Drain Fitting

Both the vent condensate drain and the heat exchanger condensate drain require a trap and must go into a sanitary

drain. (See Paragraph 7.3, pages 25-26, for requirements on installing the condensate drain.) All drain parts except the

4” PVC cap shown here are field supplied.

Model

UEAS

Installer-provided
4” Coupling
Slope downward

away from the

heater.

4” diameter

pipe

12” (305mm)

minimum

24” (610mm)

maximum

THIS PVC PIPING ARRANGEMENT APPLIES TO

U.S. INSTALLATIONS ONLY; IT DOES NOT APPLY

TO CANADIAN INSTALLATIONS.

Balance of the vent may be

either horizontal or vertical.

Slope a horizontal run down-

ward slightly toward the vent

condensate drain at the heater.

Attach installer-provided 4x4x4

PVC Tee to the 4” vent pipe outlet.

4” PVC Cap is included in the vent/combustion air kit

(Option CC2 or CC6). Cap is drilled and tapped for

field-supplied 1/2” NPT condensate drain.

Field-supplied

Drain Fitting

Both the vent condensate drain and the heat exchanger condensate drain require a trap and

must go into a sanitary drain. (See Paragraph 7.3, pages 25-26, for requirements on installing the

condensate drain.) All drain parts except the 4” PVC cap shown here are field supplied.

Model

UEAS

THIS PVC PIPING ARRANGEMENT APPLIES

TO U.S. INSTALLATIONS ONLY; IT DOES NOT

APPLY TO CANADIAN INSTALLATIONS.

FIGURE 9A - U.S.

INSTALLATION

ONLY -

Horizontal or

Vertical Vent

showing Where

to Install the

Condensate

Drain

Connection in

the Horizontal

Vent Run using

factory-provided

4” PVC Cap

12” (305mm)

minimum

24” (610mm)

maximum

Installer-provided 4” Coupling

Slope downward away from

the heater.

Model

UEAS

Field-supplied Fittings as

needed for 1/2” or larger

condensate drain line

Both the vent condensate drain and the heat exchanger condensate drain require a trap and

must go into a sanitary drain. (See Paragraph 7.3, pages 25-26, for requirements on installing

the condensate drain.) All vent and drain parts in this illustration are field supplied.

THIS PVC PIPING ARRANGEMENT APPLIES TO ALL

CANADIAN INSTALLATIONS. In Canada, all PVC vent pipe must

be approved to ULC S636. All PVC venting and drain parts in

this illustration are field supplied. This is an acceptable alternate

PVC piping arrangement for installations in the United States.

4” diameter pipe

FIGURE 8B -

CANADIAN

OR U.S.

INSTALLATION

Vertical Vent

showing Where

to Install the

Condensate

Drain

Connection

FIGURE 8A - U.S.

INSTALLATION

ONLY - Vertical

Vent showing

Where to Install

the Condensate

Drain

Connection

using factory-

provided 4”

PVC Cap

See Paragraph 7.2.1.6, page 14, for making vent pipe joints.
The vent pipe drain connects into the heater condensate drain. Refer to Paragraph

7.3, page 25, for condensate drain installation instructions.

Form I-UEAS, P/N 221232 R13, Page 13