beautypg.com

0 mechanical (cont’d), 2 venting and combustion air (cont’d) – Reznor UEAS Unit Installation Manual User Manual

Page 22

background image

1. Determine the location of the vent terminal.

Select a location away from fresh air intakes, allowing space for the concentric

adapter box inside. Vent terminal must be located from adjacent buildings as

shown in

FIGURE 20, page 24.

WARNING

All vent terminals must be positioned or located away

from fresh air intakes, doors and windows to preclude

combustion products from entering occupied space.

Failure to comply could result in severe personal injury

or death and/or property damage.

If more than one vertical concentric vent/combustion air terminal (Option CC2) is

being installed, the minimum spacing between vent centerlines is determined by

the minimum outdoor design temperature (most extreme outdoor condition at the

installation site).

Minimum Outdoor Design

Temperature

Minimum Spacing between Centerlines of Vent Pipes in

Vertical Combustion Air/Vent Terminals (Option CC2)

°F

°C

inches

mm

31 or warmer

0 or warmer

36

914

-10 to 30

-23 to -1

60

1524

less than -10 less than -23

84

2134

Installation Instructions

for Vertical Vent/

Combustion Air Kit

Option CC2

(in compliance with

requirements on

pages 12-17)

Minimum Vent Terminal

Spacing when Installing

more than one Heater

2. Install the Vent Pipe and Combustion Air Pipe Runs (from the heater to

near the location selected through the roof).

• Use the type of pipe specified in Paragraph 7.2.1.1, page 12.

• Comply with requirements in Paragraph 7.2.1.2 and 7.2.1.3, pages 12-14,

when attaching pipes to the heater when installing the condensate drain

connection.

• Overall vent length must comply with table in Paragraph 7.2.1.4, page 14.

• Make all joints according to the instructions in Paragraph 7.2.1.6, page 14-15.

Extend the runs close to the roof location selected in Step 1 above. (NOTE:

The vent pipe will extend through the roof after the concentric adapter box is

installed. The indoor combustion air pipe will end at the box.)

• Support pipes as required in Paragraph 7.2.1.7, pages 15-16.
3. Cut a clearance hole through the roof for the 8” diameter combustion air

pipe.

Position the concentric adapter box against the inside of the roof. Being sure that

the location and orientation of the box are correct, mark and cut the hole for the

8” combustion air pipe.
4. Attach the combustion air pipe to the concentric adapter box.

4a) Determine the length of the 8” outdoor combustion air pipe so that dimension

”X” in

FIGURE 17 is equal to the roof thickness plus anticipated snow depth, but

does not exceed 48” (1219mm) or have less than 18” (457mm) of pipe above the

roof.

4b) Attach the combustion air pipe to the collar of the concentric adapter box with

sheetmetal screws. Seal joint and seam with tape or sealant.
5. Attach the concentric adapter box to the underside of the roof.

(Hardware and flashing are field supplied.) On the inside, insert the combustion air

pipe up through the opening, position the box to match the pipe runs, and attach

the brackets to the roof.

7.2.3 VERTICAL VENT TERMINAL Installation - Option CC2

(cont’d)

7.2 Venting and Combustion Air (cont’d)

7.0 Mechanical

(cont’d)

Before beginning, verify that the kit is at the site and that all components are cor-

rect for the installation. Be sure all required field-supplied parts are available.

Form I-UEAS, Page 22