Carrier 39L User Manual

Page 87

background image

Example 16 — Configuration of Discrete

Temperature Control

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS

DO CTRL

Discrete temperature control
configuration subfunction of
service function

SEN 1

Controlling temperature sensor
configured to sensor 1. Sensor
codes as follows:

1 - Supply-air temperature sensor

(standard)

2 - Outdoor-air temperature

sensor (standard)

3 - Mixed-air temperature sensor

(optional)

6 - Space temperature sensor

(standard)

7 - Return-air temperature

(standard)

34 - Other optional sensors

SEN 34

Controlling temperature sensor is
34, where sensor 34 is one of
2 optional sensor types
(space temperature sensor or
duct temperature sensor)

TYP 0

Discrete output control logic
(0 = normal logic, 1 = reverse
logic)

— Used to read service history. See Example 17.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

— Used to read or change field configuration

of service maintenance alarm duration and to read elapsed
time. See Example 18.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

— Used to read timed override history. See

Example 19.

NOTE: The

key is used to enable or turn on certain

functions; the CLR key is used to disable these functions.

The

key may also be used to disable the functions.

SET POINT FUNCTION — Set points are entered through
the keyboard. Set points can be changed within the upper
and lower limits, which are fixed. See Table 17.

Example 17 — Service History Configuration

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS

SERVHIST

Service history configuration
subfunction of service function

SDAY 2

The unit had 2 starts within the
last 24 hours

ST 20

The unit had a total of 20 starts
since the unit was manufactured

FH 240

The fan has run for 240 hours
since unit manufacture.

4.06.30

The unit was last started on
Thursday at 6:30 am

4.19.00

The unit was last stopped on
Thursday at 7:00 pm

Example 18 — Service/Maintenance

Alarm Configuration

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS

SRV/MTN

Service/Maintenance alarm
configuration subfunction of
service function

SMAL 2

Service/Maintenance alarm
limit is 2000 hrs (hours x 1000)

SMAL 5

Service/Maintenance alarm
limit is changed to 5000 hrs (This
represents the cumulative number
of hours the fan must be energized
before a service/maintenance alarm
is generated)
(NOTE: Entering a . disables the
alarm function)

SMEH 3

Service/Maintenance elapsed
hours is 3000 (This is the amount of
time elapsed from the start of the
service/maintenance alarm interval)

Example 19 — Timed Override History

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS

OVRDHIST

Timed override history
subfunction of service function

OHR 3

Within the current 24 hour period
(beginning at midnight), the unit
operated for 3 hours in the timed
override mode (mode 39)

— Displays system set points. See Table 13 for

sequence of set points.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

— Displays demand limit set points.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

— Displays time of day and day of week.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

— Displays Daylight Savings Time.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

— Displays holidays (month, day, and duration).

Table 17 — Set Point Ranges and Defaults

SET POINT

ALLOWABLE

RANGE

DEFAULT

Occupied Heating Set Point (F)

40 to 90

68

Occupied Cooling Set Point (F)

45 to 99

78

Unoccupied Heating Set Point (F)

40 to 90

55

Unoccupied Cooling Set Point (F)

70 to 99

90

Static Pressure

Set Point (in. wg)

0 to 5.0

1.5

Supply-Air Temperature

Set Point (F)

35 to 65

55

Delta CFM Set Point

0 to 250

0

Humidity Set Point (%)

0 to 100

40

Analog Temperature

Control Set Point (F)

40 to 100

40

Discrete Temperature

Control Set Point (F)

−40 to 245

0

Air Quality Sensor 1

Set Point (ppm)

0 to 2000

650

Air Quality Sensor 2

Set Point (ppm)

0 to 2000

650

Outside Air Velocity Pressure

Set Point (in. wg)

0.0 to 5.0

0.08

87