Table 16 — Service Configuration Ranges and Defaults (cont)

SERVICE SUBFUNCTION

NUMBER

CONFIGURATION VALUE

RANGE

FACTORY DEFAULT

VALUE

13

Night Purge Duration (minutes)

5 to 240

15

Night Purge Low Temperature Damper Position (% output)

0 to 100

10

Night Purge High Temperature Damper Position (% output)

0 to 100

35

14

Constant Outside Air Master Proportional Gain

0.0 to 5.0

0.3

Constant Outside Air Master Integral Gain

0.0 to 5.0

1.0

Constant Outside Air Master Derivative Gain

0.0 to 5.0

0.0

Constant Outside Air Submaster Gain

60 to 600

*

OAVP Sensor Low Voltage Point

0 to 2

2

OAVP Sensor High Voltage Point

5 to 10

10

OAVP Sensor Low Voltage Reference

0.0 to 2.0

0.0

OAVP Sensor High Voltage Reference

0.01 to 5.00

0.05

OAVP Sensor Probe Multiplier Factor

0.100 to 9.999

1.564

15

Air Quality Sensor 1 Master Proportional Gain

0.01 to 1.00

0.10

Air Quality Sensor 1 Master Integral Gain

0.01 to 1.00

0.03

Air Quality Sensor 1 Maximum Damper Position (%)

0 to 100

50

Air Quality Sensor 1 Low Voltage Point

0 to 2

2

Air Quality Sensor 1 High Voltage Point

5 to 10

10

Air Quality Sensor 1 Low Voltage Reference

0 to 2000

0

Air Quality Sensor 1 High Voltage Reference

0 to 2000

2000

16

Air Quality Sensor 2 Master Proportional Gain

0.01 to 1.00

0.10

Air Quality Sensor 2 Master Integral Gain

0.01 to 1.00

0.03

Air Quality Sensor 2 Maximum Damper Position (%)

0 to 100

50

Air Quality Sensor 2 Low Voltage Point

0 to 2

2

Air Quality Sensor 2 High Voltage Point

5 to 10

10

Air Quality Sensor 2 Low Voltage Reference

0 to 2000

0

Air Quality Sensor 2 High Voltage Reference

0 to 2000

2000

17

Building Factor (%)

1 to 100

10

24 hour Unoccupied Factor

0 to 99

15

Set Point Bias (F)

0 to 10

2

Maximum Allowable Stop Time

0 to 120

60

18

Reset Ratio

0 to 10

3

Reset Limit

0 to 20

10

20

Supply Velocity Upper Limit (in. wg)

0 to 3.0

2.0

Return Velocity Upper Limit (in. wg)

0 to 3.0

2.0

Supply Duct Area

0 to 50

0

Return Duct Area

0 to 50

0

Fan Tracking Master Proportional Gain

0.0 to 2.0

0.5

Fan Tracking Master Integral Gain

0.0 to 2.0

0.5

Fan Tracking Master Derivative Gain

0.0 to 5.0

0.0

Fan Tracking Submaster Gain

−20.0 to 20.0

10.0

Fan Tracking Submaster Center Value (%)

0 to 100

50

21

Humidity Master Proportional Gain

0.0 to 10.0

2.0

Humidity Master Integral Gain

0.0 to 2.0

0.3

Humidity Master Derivative Gain

0.0 to 10.0

0.0

Humidity Submaster Gain

−20.0 to 20.0

7.5

Humidity Submaster Center Value (%)

0 to 100

50

22

Space Temperature Low Alarm Limit — Occupied (F)

−10 to 245

65

Space Temperature High Alarm Limit — Occupied (F)

−10 to 245

80

Space Temperature Low Alarm Limit — Unoccupied (F)

−10 to 245

45

Space Temperature High Alarm Limit — Unoccupied (F)

−10 to 245

100

Supply Air Temperature Low Alarm Limit — Occupied (F)

−10 to 245

45

Supply Air Temperature High Alarm Limit — Occupied (F)

−10 to 245

120

Supply Air Temperature Low Alarm Limit — Unoccupied (F)

−10 to 245

35

Supply Air Temperature High Alarm Limit — Unoccupied (F)

−10 to 245

180

Return Air Temperature Low Alarm Limit — Occupied (F)

−10 to 245

60

Return Air Temperature High Alarm Limit — Occupied (F)

−10 to 245

90

Return Air Temperature Low Alarm Limit — Unoccupied (F)

−10 to 245

35

Return Air Temperature High Alarm Limit — Unoccupied (F)

−10 to 245

120

Temperature Input Low Alarm Limit — Occupied (F)

−10 to 245

−10

Temperature Input High Alarm Limit — Occupied (F)

−10 to 245

245

Temperature Input Low Alarm Limit — Unoccupied (F)

−10 to 245

−10

Temperature Input High Alarm Limit — Unoccupied (F)

−10 to 245

245

Outside Air Temperature Low Alarm Limit (F)

−40 to 245

−40

Outside Air Temperature High Alarm Limit (F)

−40 to 245

120

Mixed Air Temperature Low Alarm Limit (F)

0 to 250

0

Mixed Air Temperature High Alarm Limit (F)

0 to 250

250

Relative Humidity Low Alarm Limit (%)

0 to 100

0

Relative Humidity High Alarm Limit (%)

0 to 100

100

Outside Air Relative Humidity Low Alarm Limit (%)

0 to 100

0

Outside Air Relative Humidity High Alarm Limit (%)

0 to 100

100

Static Pressure Low Alarm Limit (in. wg)

0 to 5.0

1.0

Static Pressure High Alarm Limit (in. wg)

0 to 5.0

2.5

Supply Velocity Low Alarm Limit (in. wg)

0 to 3.0

0.0

Supply Velocity High Alarm Limit (in. wg)

0 to 3.0

3.0

Return Velocity Low Alarm Limit (in. wg)

0 to 3.0

0.0

Return Velocity High Alarm Limit (in. wg)

0 to 3.0

3.0

Delta CFM x 100 (CCFM) Low Alarm Limit

0 to 250

0

Delta CFM x 100 (CCFM) High Alarm Limit

0 to 250

250

Air Quality Sensor 1 High Alarm Limit (ppm)

0 to 2000

800

Air Quality Sensor 2 High Alarm Limit (ppm)

0 to 2000

800

23

Preheat Coil/AOTC Master Proportional Gain

0.0 to 20.0

5.0

Preheat Coil/AOTC Master Integral Gain

0.0 to 2.0

0.3

Preheat Coil/AOTC Master Derivative Gain

0.0 to 20.0

0.0

Preheat Coil/AOTC Submaster Gain

−20.0 to 20.0

−5.0

Preheat Coil/AOTC Submaster Center Value (%)

0 to 100 F

50

Preheat Coil/AOTC Fan/Off Value (F)

35 to 65

40

Preheat Coil/AOTC Sensor

0 to 128

0

24

Discrete Temperature Control Sensor

0 to 128

0

Discrete Temperature Control Logic

0 to 1

0

Discrete Temperature Control Hysteresis (F)

0 to 20

2

26

Service/Maintenance Limits (hours x 1000)

0 to 99

0

Service/Maintenance Elapsed Hours (hours x 1000)

0 to 99

0

LEGEND

AOTC — Analog Output Temperature Control
OAVP

Outside Air Velocity Pressure

83