Table 13 — Keyboard Directory (cont)

SERVICE CONFIGURATIONS

Keyboard Entry

Display

Description

AIRQUAL1

Configuration of indoor air quality
and AQ sensor no. 1

MPG X

Master proportional gain

MIG X

Master integral gain

XDP X

Maximum damper position

Q1LV X

Air quality sensor 1 low voltage
point

Q1HV X

Air quality sensor 1 high voltage
point

Q1LR X

Air quality sensor 1 low voltage
reference

Q1HR X

Air quality sensor 1 high voltage
reference

MDP X

Minimum damper position

AIRQUAL2

Configuration of indoor air quality
and AQ sensor no. 2

MPG X

Master proportional gain

MIG X

Master integral gain

XDP X

Maximum damper position

Q2LV X

Air quality sensor 2 low voltage point

Q2HV X

Air quality sensor 2 high voltage point

Q2LR X

Air quality sensor 2 low voltage reference

Q2HR X

Air quality sensor 2 high voltage reference

MDP X

Minimum damper position

AOSS X

Configuration of optimal start/stop

BLDF X

Building factor

UOCF X

24 hour occupied factor

SETB X

Set point bias

OSMT X

Maximum allowable stop time

SPRESET

Configuration of space temperature reset

RTIO X

Reset ratio X

LIMT X

Reset limit X

LOADSHED Configuration of loadshed

LSGP X

Loadshed group number (1-16)

FANTRACK

Configuration of fan tracking

SVUL X

Supply velocity upper limit

RVUL X

Return velocity upper limit

SDAR X

Supply duct area

RDAR X

Return duct area

MPG X

Master proportional gain

MIG X

Master integral gain

MDG X

Master derivative gain

SMG X

Submaster gain

SCV X

Submaster center value

SMR X

Submaster reference value

SMR X

Submaster reference value forced

SERVICE CONFIGURATIONS

Keyboard Entry

Display

Description

HUMIDITY

Configuration of humidity

MPG X

Master proportional gain

MIG X

Master integral gain

MDG X

Master derivative gain

SMG X

Submaster gain

SCV X

Submaster center value

SMR X

Submaster reference value

SMR X

Submaster reference value forced

ALRMLIMT

Configuration of alarm limits

SPLO X

Space temperature low alarm limit/
occupied

SPHO X

Space temperature high alarm limit/
occupied

SPLU X

Space temperature low alarm limit/
unoccupied

SPHU X

Space temperature high alarm limit/
unoccupied

SALO X

Supply air temperature low alarm limit/
occupied

SAHO X

Supply air temperature high alarm limit/
occupied

SALU X

Supply air temperature low alarm limit/
unoccupied

SAHU X

Supply air temperature high alarm limit/
unoccupied

RALO X

Return air temperature low alarm limit/
occupied

RAHO X

Return air temperature high alarm limit/
occupied

RALU X

Return air temperature low alarm limit/
unoccupied

RAHU X

Return air temperature high alarm limit/
unoccupied

TLO X

Temperature input low alarm limit/
occupied

THO X

Temperature input high alarm limit/
occupied

TLU X

Temperature input low alarm limit/
unoccupied

THU X

Temperature input high alarm limit/
unoccupied

OATL X

Outside air temperature low alarm limit

OATH X

Outside air temperature high alarm limit

MATL X

Mixed air temperature low alarm limit

MATH X

Mixed air temperature high alarm limit

RHL X

Relative humidity low alarm limit

RHH X

Relative humidity high alarm limit

ORHL X

Outside air relative humidity low alarm
limit

ORHH X

Outside air relative humidity high alarm
limit

SPL X

Static pressure low alarm limit

SPH X

Static pressure high alarm limit

SVPL X

Supply velocity pressure low alarm limit

SVPH X

Supply velocity pressure high alarm limit

RVPL X

Return velocity pressure low alarm limit

RVPH X

Return velocity pressure high alarm limit

CFML X

Delta CFM x 100 low alarm limit

CFMH X

Delta CFM x 100 high alarm limit

Q1H X

Air quality sensor 1 high alarm limit

Q2H X

Air quality sensor 2 high alarm limit

74