— Used to read or change field configuration

of fan tracking. See Example 13.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

— Used to read or change factory configura-

tion of humidity control.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

— Used to read or change factory configura-

tion of alarm limits. See Example 14.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

— Used to read or change field configuration

of analog temperature control. See Example 15.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

— Used to read or change field configuration

of discrete temperature control. See Example 16.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Example 13 — Configuration of Fan Tracking

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS

FANTRACK

Fan tracking field configuration
subfunction of service function

SVUL 1.5

Supply velocity upper limit
= 1.5 in. wg

SVUL 2.0

Supply velocity upper limit
changed to 2.0 in. wg

RVUL 1.5

Scroll past return velocity upper
limit (1.5 in. wg)

SDAR 0

Supply duct area = 0

SDAR 8

Supply duct area changed to
8 sq ft. (Enter whole numbers;
decimals not accepted)

RDAR 6

Scroll past return duct area
(6 sq ft)

MPG 0.5

Scroll past master proportional
gain

MIG 0.5

Scroll past master integral
gain

MDG 0.0

Master derivative gain

MDG 4

Master derivative gain
changed to 4

SMG 10

Scroll past submaster gain

SCV 50

Scroll past submaster
gain center value

SMR N

Submaster reference value
(calculated and updated by the
software)

SMR X

Submaster reference value
forced to X value

SMR N

Submaster reference value
force is removed

Example 14 — Configuration of Alarm Limits

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS

ALRMLIMT

Alarm limit field configuration of
subfunction of service function

SPLO 65

Scroll past space temperature low
limit (occupied mode)

SPHO 80

Scroll past space temperature high
limit (occupied mode)

SPLU 45

Scroll past space air temperature
low limit (unoccupied mode)

SPHU 100

Scroll past space air temperature
high limit (unoccupied mode)

SALO 45

Supply-air temperature low limit set
at 45 F (occupied mode)

SALO N

Supply-air temperature low limit
changed to N, where N = new
value within allowable range
(−10 F to 245 F)

Example 15 — Configuration of Analog

Temperature Control

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS

AO CTRL

Analog temperature control
configuration subfunction of
service function

MPG 5.0

Scroll past master proportional
gain

MIG 0.3

Scroll past master integral gain

MDG 0.0

Scroll past master derivative gain

SMG −5.0

Scroll past submaster gain

SCV 50

Scroll past submaster center
value

FOV 40

Scroll past fan OFF value

SEN 0

Controlling temperature sensor
(none configured)

SEN 1

Controlling temperature sensor
configured to sensor 1. Sensor
codes as follows:

1 - Supply-air temperature sensor

(standard)

2 - Outdoor-air temperature

sensor (standard)

3 - Mixed-air temperature sensor

(optional)

6 - Space temperature sensor

(standard)

7 - Return-air temperature sensor

(standard)

34 - Other optional sensor

SMR X

Submaster reference value

SMR N

Submaster reference value
forced to N value

SMR X

Force removed from submaster
reference value. Display shows
last value prior to force