Table 16 — Service Configuration Ranges and Defaults

SERVICE

SUBFUNCTION

NUMBER

CONFIGURATION VALUE

RANGE

FACTORY

DEFAULT

VALUE

3

Unit Type (0 = CV, 1 = VAV)

0/1

0

Cooling Type (0 = none, 1 = chilled water coil, 2 = DX)

0 to 2

1

DX Cooling Stages

0 to 8

2

Heating Type (0 = none, 1 = hot water/steam coil,
2 = electric heater)

0 to 2

1

Electric Heater Stages

0 to 8

0

Mixed Air Dampers (0 = none, 1 = analog,
2 = 2-position)

0 to 2

1

Indoor-Air Quality Type (1 = single gas, 2 = differential/2 gases)

1/2

1

Mixed-Air Temperature Protection

Yes/No

Yes

Bus Number

0 to 239

0

Element Address

0 to 239

1

Password

0 to 9999

1111

4

English/Metric System (0 = English, 1 = Metric)

0/1

0

5

Nighttime Free Cooling

Enabled/Disabled

Disabled

Humidity Control (0 = none, 1 = analog, 2 = discrete)

0 to 2

0

Occupied Heating

Enabled/Disabled

Disabled

Space Temperature Reset

Enabled/Disabled

Disabled

Demand Limit

Enabled/Disabled

Disabled

Fan Tracking

Enabled/Disabled

Disabled

Constant Outside Air

Enabled/Disabled

Disabled

Night Purge

Enabled/Disabled

Disabled

Indoor Air Quality

Enabled/Disabled

Disabled

Indoor Air Quality Priority Level (high = 1, low = 2, none = 3)

1 to 3

2

Adaptive Optimal Start/Stop

Enabled/Disabled

Disabled

Timed Override Schedules

1 to 3

1

(1 = Time schedule no. 1, 2 = Time schedule no. 2, 3 = Both)
Timed Override Hours

0 to 4

0

6

Heating Coil Master Proportional Gain

0 to 20.0

8.0

Heating Coil Master Integral Gain

0 to 2.0

0.3

Heating Coil Master Derivative Gain

0 to 20.0

0.0

Heating Coil Submaster Gain

−20.0 to 20.0

−7.5

Heating Coil Submaster Center Value (%)

0 to 100

50

Heating Coil Fan ‘‘Off’’ Value (F)

35 to 65

40

7

Cooling Master Proportional Gain

0 to 20.0

8.0

Cooling Master Integral Gain

0 to 2.0

0.3

Cooling Master Derivative Gain

0 to 20.0

0.0

Cooling Coil Submaster Gain

−20.0 to 20.0

−7.5

Cooling Coil Submaster Center Value (%)

0 to 100

80

Cooling High Humidity Limit (%)

0 to 99

99

8

DX Cooling Submaster Gain

2.0 to 25.0

*

DX Cooling Minimum Submaster Reference

0 to 60

40

DX Cooling Stage 1 Time Guard

Device (0 = disabled,

1 = enabled)

Enabled/Disabled

Enabled

DX Cooling Stage 2 Time Guard (0 = disabled, 1 = enabled)

Enabled/Disabled

Enabled

DX Cooling Stage 3 Time Guard (0 = disabled, 1 = enabled)

Enabled/Disabled

Enabled

DX Cooling Stage 4 Time Guard (0 = disabled, 1 = enabled)

Enabled/Disabled

Enabled

DX Cooling Stage 5 Time Guard (0 = disabled, 1 = enabled)

Enabled/Disabled

Enabled

DX Cooling Stage 6 Time Guard (0 = disabled, 1 = enabled)

Enabled/Disabled

Enabled

DX Cooling Stage 7 Time Guard (0 = disabled, 1 = enabled)

Enabled/Disabled

Enabled

DX Cooling Stage 8 Time Guard (0 = disabled, 1 = enabled)

Enabled/Disabled

Enabled

DX Cooling Stage 1 Logic Type (0 = normal, 1 = inverted)

Normal/Inverted

Normal

DX Cooling Stage 2 Logic Type (0 = normal, 1 = inverted)

Normal/Inverted

Normal

DX Cooling Stage 3 Logic Type (0 = normal, 1 = inverted)

Normal/Inverted

Normal

DX Cooling Stage 4 Logic Type (0 = normal, 1 = inverted)

Normal/Inverted

Normal

DX Cooling Stage 5 Logic Type (0 = normal, 1 = inverted)

Normal/Inverted

Normal

DX Cooling Stage 6 Logic Type (0 = normal, 1 = inverted)

Normal/Inverted

Normal

DX Cooling Stage 7 Logic Type (0 = normal, 1 = inverted)

Normal/Inverted

Normal

DX Cooling Stage 8 Logic Type (0 = normal, 1 = inverted)

Normal/Inverted

Normal

9

Inlet Guide Vanes Master Proportional Gain

0 to 5.0

0.5

Inlet Guide Vanes Master Integral Gain

0 to 2.0

0.3

Inlet Guide Vanes Master Derivative Gain

0 to 5.0

0.0

Inlet Guide Vanes Submaster Gain

−10.0 to 10.0

5.0

Inlet Guide Vanes Submaster Center Value (%)

0 to 100

50

10

Mixed-Air Damper Master Proportional Gain

0 to 20.0

8.0

Mixed-Air Damper Master Integral Gain

0 to 2.0

0.3

Mixed-Air Damper Master Derivative Gain

0 to 20.0

0.0

Mixed-Air Damper Submaster Gain

−20.0 to 20.0

−7.5

Mixed-Air Damper Submaster Center Value (%)

0 to 100

50

Mixed-Air Damper Minimum Position (%)

0 to 100

10

11

Electric Heat Master Proportional Gain

0 to 20.0

8.0

Electric Heat Master Integral Gain

0 to 2.0

0.3

Electric Heat Master Derivative Gain

0 to 20.0

0.0

Electric Heat Submaster Gain

0 to 15.0

5.0

12

NTFC Lock Out Temperature (F)

40 to 70

50

LEGEND

CV

Constant Volume

DX

Direct Expansion

NTFC — Nighttime Free Cooling
VAV

Variable Air Volume

*Value varies and is automatically calculated by the control. Override this feature by forcing the value.

82