Carrier 39L User Manual
Page 82
Table 16 — Service Configuration Ranges and Defaults
SERVICE
SUBFUNCTION
NUMBER
CONFIGURATION VALUE
RANGE
FACTORY
DEFAULT
VALUE
3
Unit Type (0 = CV, 1 = VAV)
0/1
0
Cooling Type (0 = none, 1 = chilled water coil, 2 = DX)
0 to 2
1
DX Cooling Stages
0 to 8
2
Heating Type (0 = none, 1 = hot water/steam coil,
2 = electric heater)
0 to 2
1
Electric Heater Stages
0 to 8
0
Mixed Air Dampers (0 = none, 1 = analog,
2 = 2-position)
0 to 2
1
Indoor-Air Quality Type (1 = single gas, 2 = differential/2 gases)
1/2
1
Mixed-Air Temperature Protection
Yes/No
Yes
Bus Number
0 to 239
0
Element Address
0 to 239
1
Password
0 to 9999
1111
4
English/Metric System (0 = English, 1 = Metric)
0/1
0
5
Nighttime Free Cooling
Enabled/Disabled
Disabled
Humidity Control (0 = none, 1 = analog, 2 = discrete)
0 to 2
0
Occupied Heating
Enabled/Disabled
Disabled
Space Temperature Reset
Enabled/Disabled
Disabled
Demand Limit
Enabled/Disabled
Disabled
Fan Tracking
Enabled/Disabled
Disabled
Constant Outside Air
Enabled/Disabled
Disabled
Night Purge
Enabled/Disabled
Disabled
Indoor Air Quality
Enabled/Disabled
Disabled
Indoor Air Quality Priority Level (high = 1, low = 2, none = 3)
1 to 3
2
Adaptive Optimal Start/Stop
Enabled/Disabled
Disabled
Timed Override Schedules
1 to 3
1
(1 = Time schedule no. 1, 2 = Time schedule no. 2, 3 = Both)
Timed Override Hours
0 to 4
0
6
Heating Coil Master Proportional Gain
0 to 20.0
8.0
Heating Coil Master Integral Gain
0 to 2.0
0.3
Heating Coil Master Derivative Gain
0 to 20.0
0.0
Heating Coil Submaster Gain
−20.0 to 20.0
−7.5
Heating Coil Submaster Center Value (%)
0 to 100
50
Heating Coil Fan ‘‘Off’’ Value (F)
35 to 65
40
7
Cooling Master Proportional Gain
0 to 20.0
8.0
Cooling Master Integral Gain
0 to 2.0
0.3
Cooling Master Derivative Gain
0 to 20.0
0.0
Cooling Coil Submaster Gain
−20.0 to 20.0
−7.5
Cooling Coil Submaster Center Value (%)
0 to 100
80
Cooling High Humidity Limit (%)
0 to 99
99
8
DX Cooling Submaster Gain
2.0 to 25.0
*
DX Cooling Minimum Submaster Reference
0 to 60
40
DX Cooling Stage 1 Time Guard
ா
Device (0 = disabled,
1 = enabled)
Enabled/Disabled
Enabled
DX Cooling Stage 2 Time Guard (0 = disabled, 1 = enabled)
Enabled/Disabled
Enabled
DX Cooling Stage 3 Time Guard (0 = disabled, 1 = enabled)
Enabled/Disabled
Enabled
DX Cooling Stage 4 Time Guard (0 = disabled, 1 = enabled)
Enabled/Disabled
Enabled
DX Cooling Stage 5 Time Guard (0 = disabled, 1 = enabled)
Enabled/Disabled
Enabled
DX Cooling Stage 6 Time Guard (0 = disabled, 1 = enabled)
Enabled/Disabled
Enabled
DX Cooling Stage 7 Time Guard (0 = disabled, 1 = enabled)
Enabled/Disabled
Enabled
DX Cooling Stage 8 Time Guard (0 = disabled, 1 = enabled)
Enabled/Disabled
Enabled
DX Cooling Stage 1 Logic Type (0 = normal, 1 = inverted)
Normal/Inverted
Normal
DX Cooling Stage 2 Logic Type (0 = normal, 1 = inverted)
Normal/Inverted
Normal
DX Cooling Stage 3 Logic Type (0 = normal, 1 = inverted)
Normal/Inverted
Normal
DX Cooling Stage 4 Logic Type (0 = normal, 1 = inverted)
Normal/Inverted
Normal
DX Cooling Stage 5 Logic Type (0 = normal, 1 = inverted)
Normal/Inverted
Normal
DX Cooling Stage 6 Logic Type (0 = normal, 1 = inverted)
Normal/Inverted
Normal
DX Cooling Stage 7 Logic Type (0 = normal, 1 = inverted)
Normal/Inverted
Normal
DX Cooling Stage 8 Logic Type (0 = normal, 1 = inverted)
Normal/Inverted
Normal
9
Inlet Guide Vanes Master Proportional Gain
0 to 5.0
0.5
Inlet Guide Vanes Master Integral Gain
0 to 2.0
0.3
Inlet Guide Vanes Master Derivative Gain
0 to 5.0
0.0
Inlet Guide Vanes Submaster Gain
−10.0 to 10.0
5.0
Inlet Guide Vanes Submaster Center Value (%)
0 to 100
50
10
Mixed-Air Damper Master Proportional Gain
0 to 20.0
8.0
Mixed-Air Damper Master Integral Gain
0 to 2.0
0.3
Mixed-Air Damper Master Derivative Gain
0 to 20.0
0.0
Mixed-Air Damper Submaster Gain
−20.0 to 20.0
−7.5
Mixed-Air Damper Submaster Center Value (%)
0 to 100
50
Mixed-Air Damper Minimum Position (%)
0 to 100
10
11
Electric Heat Master Proportional Gain
0 to 20.0
8.0
Electric Heat Master Integral Gain
0 to 2.0
0.3
Electric Heat Master Derivative Gain
0 to 20.0
0.0
Electric Heat Submaster Gain
0 to 15.0
5.0
12
NTFC Lock Out Temperature (F)
40 to 70
50
LEGEND
CV
— Constant Volume
DX
— Direct Expansion
NTFC — Nighttime Free Cooling
VAV
— Variable Air Volume
*Value varies and is automatically calculated by the control. Override this feature by forcing the value.