beautypg.com

Carrier 39L User Manual

Page 58

background image

ANALOG DEVICE FOR ANALOG OUTPUT TEMPERA-
TURE CONTROL — The analog controlled device selected
must be capable of receiving a 4 to 20 mA signal. Its internal
impedance must not exceed 600 ohms.

The power supply of the analog device must be field in-

stalled.

Using a 20 AWG twisted wire pair, wire the control signal

as follows (Fig. 51).
1. Connect the positive (

ϩ) contact to pin 46 of the option

module.

2. Connect the negative (−) contact to pin 47 of the option

module.

DEVICE UNDER DISCRETE OUTPUT TEMPERATURE
CONTROL — The factory-supplied SPDT relay must be field
installed and wired. See Fig. 52. The relay contacts are rated
as follows:

48 va at 24 vac and .25 power factor

125 va at 115 vac and .25 power factor
125 va at 230 vac and .25 power factor

The relay provides a set of contacts (normally open and nor-
mally closed) using no. 6 screw terminals while the 24 vdc
coil connections are through

1

4

-in. quick connects.

Using a 20 AWG twisted cable, connect the relay coil con-

tacts 1 and 2 to the option module pins 50 and 51. Connect
the device to be controlled to the normally-open or normally-
closed contacts of the relay. Pay close attention to the con-
tact ratings listed above. See Fig. 53.

DISCRETE OUTPUT DEVICE UNDER TIMECLOCK
CONTROL — The factory-supplied SPDT relay must be field
installed and wired. (Fig. 52.) The relay contacts are rated as
follows:

48 va at 24 vac and .25 power factor

125 va at 115 vac and .25 power factor
125 va at 230 vac and .25 power factor

The relay provides a set of contacts (normally open and nor-
mally closed) using no. 6 screw terminals while the 24 vdc
coil connections are through

1

4

-in. quick connects.

Using a 20 AWG twisted cable, connect the relay coil con-

tacts to the option module pins 53 and 54. Connect the de-
vice to be controlled to the normally-open or normally-
closed contacts of the relay. Pay close attention to the contact
ratings listed above. See Fig. 54.

Field Wiring

Fig. 51 — Wiring of Analog Device for Analog Output Temperature Control

NC

SDA

2

0

2

0

COM

NO

1

COI L

2

Fig. 52 — Single-Pole, Double-Throw (SPDT) Relay

58