Table 13 — Keyboard Directory (cont)

SCHEDULE

Keyboard Entry

Display

Description

OVRD X

Number of hours to extend
occupied mode of schedule 1

PERIOD 1

Define period 1 of time
schedule 1

OCC X

Start of occupied time

UNO X

Start of unoccupied time

MON X

Monday flag (x = entry code)
(1 = yes, .0 or CLR = no)

TUE X

Tuesday flag (x = entry code)
(1 = yes, .0 or CLR = no)

WED X

Wednesday flag (x = entry code)
(1 = yes, .0 or CLR = no)

THU X

Thursday flag (x = entry code)
(1 = yes, .0 or CLR = no)

FRI X

Friday flag (x = entry code)
(1 = yes, .0 or CLR = no)

SAT X

Saturday flag (x = entry code)
(1 = yes, .0 or CLR = no)

SUN X

Sunday flag

HOL X

Holiday flag

Time periods 2-8 of schedule 1

(same elements as period 1, schedule 1)

OVRD X

Number of hours to extend
occupied mode of schedule 2

PERIOD 1

Define period 1 of time
schedule 2

OCC X

Start of occupied time

UNO X

Start of unoccupied time

MON X

Monday flag (x = entry code)
(1 = yes, .0 or CLR = no)

TUE X

Tuesday flag (x = entry code)
(1 = yes, .0 or CLR = no)

WED X

Wednesday flag (x = entry code)
(1 = yes, .0 or CLR = no)

THU X

Thursday flag (x = entry code)
(1 = yes, .0 or CLR = no)

FRI X

Friday flag (x = entry code)
(1 = yes, .0 or CLR = no)

SAT X

Saturday flag (x = entry code)
(1 = yes, .0 or CLR = no)

SUN X

Sunday flag

HOL X

Holiday flag

Time periods 2-8 of schedule 2

(same elements as period 1, schedule 2)

CV

Constant Volume

DX

Direct Expansion

VAV — Variable Air Volume

SERVICE CONFIGURATIONS

Keyboard Entry

Display

Description

LOG ON

Enter password to log on

LOGGEDON Log on okay

When finished with configuration, log off as follows:

LOGGEDON

Shows that configurations are
available

LOG OFF

LOGD OFF

Log off okay; configurations again
password protected

VERSION

Software version

XXX-XX-X

Software version number

FACT CFG

Factory configuration

TYPE X

Unit type (0 = CV, 1 = VAV)

COOL X

Cooling (0 = none, 1 = coil)

DXST X

DX cooling stages 0-8
(enter number)

HEAT X

Heating (0 = none,
1 = hot/steam,
2 = electric heat coil)

EHST X

Electric heat stages 0-8
(enter number)

MIXD X

Mixed air damper (0 = none,
1 = yes, 2 = 2-position)

IAQT X

Indoor-air quality type

MATP X

Mixed air temperature protection

BUS X

Bus number (factory default
set = 0)

ADR X

Element address (factory set
default = 1)

PSW X

Password XXXX

UNITS X

English/metric system
(0 = English, 1 = metric)

USER CFG

User configuration

NTEN X

Nighttime free cooling
configuration

HUEN X

Humidity configuration

OHEN X

Occupied heating configuration

RSEN X

Space temperature reset
configuration

DLEN X

Demand limiting configuration

FTEN X

Fan tracking configuration

OAEN X

Constant outside air

NPEN X

Night purge

AQEN X

Indoor air quality

IAQP X

Indoor air quality priority level

OSEN X

Optimal start/stop configuration

TSCH X

Timed override schedules

TOVR X

Timed override values

HEATCOIL

Configuration of heating coil

MPG X

Master proportional gain

MIG X

Master integral gain

MDG X

Master derivative gain

SMG X

Submaster gain

SCV X

Submaster center value

FOV X

Fan off value

SMR X

Submaster reference value

SMR X

Submaster reference value forced