Table 13 — keyboard directory (cont) – Carrier 39L User Manual
Page 72

Table 13 — Keyboard Directory (cont)
SCHEDULE
Keyboard Entry
Display
Description
OVRD X
Number of hours to extend
occupied mode of schedule 1
PERIOD 1
Define period 1 of time
schedule 1
OCC X
Start of occupied time
UNO X
Start of unoccupied time
MON X
Monday flag (x = entry code)
(1 = yes, .0 or CLR = no)
TUE X
Tuesday flag (x = entry code)
(1 = yes, .0 or CLR = no)
WED X
Wednesday flag (x = entry code)
(1 = yes, .0 or CLR = no)
THU X
Thursday flag (x = entry code)
(1 = yes, .0 or CLR = no)
FRI X
Friday flag (x = entry code)
(1 = yes, .0 or CLR = no)
SAT X
Saturday flag (x = entry code)
(1 = yes, .0 or CLR = no)
SUN X
Sunday flag
HOL X
Holiday flag
Time periods 2-8 of schedule 1
(same elements as period 1, schedule 1)
OVRD X
Number of hours to extend
occupied mode of schedule 2
PERIOD 1
Define period 1 of time
schedule 2
OCC X
Start of occupied time
UNO X
Start of unoccupied time
MON X
Monday flag (x = entry code)
(1 = yes, .0 or CLR = no)
TUE X
Tuesday flag (x = entry code)
(1 = yes, .0 or CLR = no)
WED X
Wednesday flag (x = entry code)
(1 = yes, .0 or CLR = no)
THU X
Thursday flag (x = entry code)
(1 = yes, .0 or CLR = no)
FRI X
Friday flag (x = entry code)
(1 = yes, .0 or CLR = no)
SAT X
Saturday flag (x = entry code)
(1 = yes, .0 or CLR = no)
SUN X
Sunday flag
HOL X
Holiday flag
Time periods 2-8 of schedule 2
(same elements as period 1, schedule 2)
CV
— Constant Volume
DX
— Direct Expansion
VAV — Variable Air Volume
SERVICE CONFIGURATIONS
Keyboard Entry
Display
Description
LOG ON
Enter password to log on
LOGGEDON Log on okay
When finished with configuration, log off as follows:
LOGGEDON
Shows that configurations are
available
LOG OFF
LOGD OFF
Log off okay; configurations again
password protected
VERSION
Software version
XXX-XX-X
Software version number
FACT CFG
Factory configuration
TYPE X
Unit type (0 = CV, 1 = VAV)
COOL X
Cooling (0 = none, 1 = coil)
DXST X
DX cooling stages 0-8
(enter number)
HEAT X
Heating (0 = none,
1 = hot/steam,
2 = electric heat coil)
EHST X
Electric heat stages 0-8
(enter number)
MIXD X
Mixed air damper (0 = none,
1 = yes, 2 = 2-position)
IAQT X
Indoor-air quality type
MATP X
Mixed air temperature protection
BUS X
Bus number (factory default
set = 0)
ADR X
Element address (factory set
default = 1)
PSW X
Password XXXX
UNITS X
English/metric system
(0 = English, 1 = metric)
USER CFG
User configuration
NTEN X
Nighttime free cooling
configuration
HUEN X
Humidity configuration
OHEN X
Occupied heating configuration
RSEN X
Space temperature reset
configuration
DLEN X
Demand limiting configuration
FTEN X
Fan tracking configuration
OAEN X
Constant outside air
NPEN X
Night purge
AQEN X
Indoor air quality
IAQP X
Indoor air quality priority level
OSEN X
Optimal start/stop configuration
TSCH X
Timed override schedules
TOVR X
Timed override values
HEATCOIL
Configuration of heating coil
MPG X
Master proportional gain
MIG X
Master integral gain
MDG X
Master derivative gain
SMG X
Submaster gain
SCV X
Submaster center value
FOV X
Fan off value
SMR X
Submaster reference value
SMR X
Submaster reference value forced
72