Table 15 — State of Items Controlled

MODE

(DISPLAY

CODE)

RETURN

FAN

SUPPLY

FAN

OUTDOOR-

AIR

DAMPER

RETURN-

AIR

DAMPER

EXHAUST

DAMPER

SUPPLY FAN

INLET GUIDE

VANES (IGV)

RETURN

FAN IGV

HEAT

INTERLOCK

RELAY

ELECTRIC

HEAT ALL

STAGES

Pressurization

(34)

Off

On

Open

Close

Close

Open to

Static Pressure

Set Point

Close

On

Off

Purge

(36)

On

On

Open

Close

Open

Open to

Static Pressure

Set point

Open to

л ⌬

cfm

On

Off

Evacuation

(35)

On

Off

Close

Close

Open

Close

Open

Off

Off

Fire Shutdown

(37)

Off

Off

Close

Open

Close

Close

Close

Off

Off

(Set point) — This subfunction displays the current

operating system set points.

To view set points, depress

, then use the

key

to display the occupied heat set point. Continue to depress

to display all the various system set points. Table 13

shows the order of the various set points.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

(Inputs) — The inputs subfunction displays the read-

ings at the various temperature sensors, fan status, static pres-
sure sensors, enthalpy switch, and freezestat. It also allows
the outside-air temperature sensor, enthalpy switch, return-
air relative humidity sensor, outside-air relative hu-
midity sensor, and filter status to be forced to a user deter-
mined value or status. The forced value overrides the value
that the control system actually reads. This permits opera-
tion in the event of a faulty sensor.

To read a sensor, enter

, then scroll to the de-

sired sensor reading using the

key. To force an input,

see Example 3. Table 13 shows the order of the readouts.

Example 3 — Forcing An Input Value

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS

INPUTS

System inputs

Scroll past:

SPT X

Space temperature

SAT X

Supply air temperature

RT X

Return air temperature

MAT X

Mixed air temperature

OAT 60

Outside air temperature

8

0

OAT 80/FORCED

Outside air temperature value
forced to 80. NOTE: Forced
value toggles between value
and word forced

OAT 60

Outside air temperature
forced value removed.
Display no longer flashes

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

(Outputs) — The output subfunction displays or

forces the output value percentage of the inlet guide vanes,
mixed air damper and heating and cooling valves. It also
displays or forces the ON/OFF status of the supply fan and
heat interlock relay, displays the status of electric heat stages,
and displays optional output status for return fan volume con-
trol, analog output temperature control, discrete output tem-
perature control, discrete output time clock, and humidifier
stages.

To read a system output value, enter

, then scroll

to the desired output using the

key. To force a system

output value, see Example 4. Table 13 shows the order of
the output values.

Example 4 — Forcing An Output Value

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS

OUTPUTS

System Outputs

Scroll past:

IGV X

Inlet guide vanes

MIXD X

Mixed air damper

HCV X

Heating coil valve

CCV X

Cooling coil valve

SF OFF

Supply fan off

SF ON/FORCED

Supply fan forced ON.
NOTE: Supply fan forced
value toggles between value
(SF ON) and word FORCED

SF OFF

Supply fan forced value re-
moved. Display no longer flashes

HISTORY FUNCTION

— Displays the 9 latest alarms generated by the

unit in the order of their occurrence. If 9 alarms are dis-
played, the occurrence of a 10th alarm shifts the first alarm
off the display.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -