Table 13 — Keyboard Directory (cont)

STATUS

Keyboard Entry

Display

Description

INPUTS

System inputs

SPT X

Space temperature

SAT X

Supply air temperature

RAT X

Return air temperature

OAT X

Outside air temperature

OAT X

Outside air temperature forced
(x = forced value)

SP X

Static pressure

SFS X

Supply fan status

ENT X

Enthalpy switch status

ENT X

Enthalpy switch status forced
(x = forced value)

RH X

Relative humidity

RH X

Relative humidity forced
(x = forced value)

FRZ X

Freezestat status

MAT X

Mixed air temperature

OARH X

Outside air relative humidity

OARH X

Outside air relative humidity forced
(x = forced value)

FLTS X

Filter status

FLTS X

Filter status forced
(x = forced value)

TEMP X

Temperature input

RVP X

Return velocity pressure

SVP X

Supply velocity pressure

DHH X

Duct high humidity

EVAC X

Evacuation

PRES X

Pressurization

PURG X

Smoke purge

FSD X

Fire shutdown

MTR X

Meter

OAVP X

Outdoor air velocity pressure

OAVP X

Outdoor air velocity pressure
(x = forced value)

AQ1 X

Air quality 1

AQ1 X

Air quality 1
(x = forced value)

AQ2 X

Air quality 2

AQ2 X

Air quality 2
(x = forced value)

CUST X

Condensing unit status

CUST X

Condensing unit status
(x = forced value)

DXSD X

DX cooling shutdown

DXSD X

DX cooling shutdown
(x = forced value)

OUTPUTS

System outputs

IGV X

Inlet guide vanes

DX — Direct Expansion

STATUS

Keyboard Entry

Display

Description

IGV X

Inlet guide vanes forced
(x = forced value)

MIXD X

Mixed air damper

MIXD X

Mixed air damper forced
(x = forced value)

HCV X

Heating coil valve

HCV X

Heating coil valve forced
(x = forced value)

CCV X

Cooling coil valve

CCV X

Cooling coil valve forced
(x = forced value)

SF X

Supply fan start/stop

SF X

Supply fan start/stop forced
(x = forced value)

HIR X

Heat interlock relay

HIR X

Heat interlock relay forced
(x = forced value)

EHS1 X

Electric heat stage 1

EHS2 X

Electric heat stage 2

EHS3 X

Electric heat stage 3

EHS4 X

Electric heat stage 4

EHS5 X

Electric heat stage 5

EHS6 X

Electric heat stage 6

EHS7 X

Electric heat stage 7

EHS8 X

Electric heat stage 8
(NOTE: Only the actual number of
heater stages applicable to the unit
are provided.)

RFVC X

Return fan volume

RFVC X

Return fan volume forced
(x = forced value)

HUM1 X

Humidifier first stage

HUM1 X

Humidifier first stage forced
(x = forced value)

HUM2 X

Humidifier 2nd stage

HUM2 X

Humidifier 2nd stage forced
(x = forced value)

AOTC X

Analog temperature

AOTC X

Analog temperature forced
(x = forced value)

DOTC X

Discrete temperature

DOTC X

Discrete temperature forced
(x = forced value)

DTCC X

Discrete time clock

DTCC X

Discrete time clock forced
(x = forced value)

DXS1 X

DX cooling stage 1

DXS2 X

DX cooling stage 2

DXS3 X

DX cooling stage 3

DXS4 X

DX cooling stage 4

DXS5 X

DX cooling stage 5

DXS6 X

DX cooling stage 6

DXS7 X

DX cooling stage 7

DXS8 X

DX cooling stage 8