beautypg.com

Carrier 39L User Manual

Page 79

background image

Occupied Cooling (31) — Indicates that the unit is in the
Cooling mode to satisfy its Occupied Cooling set point.
Occupied Fan Only (32) — Indicates that the unit is main-
taining set point by using a mixture of outside and return air
only. No mechanical heating or cooling is being used.
Nighttime Free Cooling (33) — Indicates that the supply fan
is on and using outside air to precool the space served by the
unit. Unit must be configured for nighttime free cool-

ing (

). (This mode is enabled by

.)

Smoke Pressurization (34) — Indicates that the unit is in the
Pressurization mode. This mode is issued from the fire
system panel. Refer to Table 15 for the state of the items
controlled.
Smoke Evacuation (35) — Indicates that the unit is in the
Smoke Evacuation mode. This mode is issued from the
system panel. Refer to Table 15 for the state of the items
controlled.
Smoke Purge (36) — Indicates that the unit is in the Smoke
Purge mode. This mode is issued from the fire system panel.
Refer to Table 15 for the state of the items controlled.
Fire Shutdown (37) — Indicates that the unit is in the Fire
Shutdown mode. This mode is issued from the fire system
panel or local smoke detector. Refer to Table 15 for the state
of the items controlled.
Quick Test (38) — Indicates that the unit is in the Quick Test
mode. It allows the user to test all inputs and outputs con-
nected to the PIC controller. All control routines are deac-
tivated when the unit is in this mode. This mode can only be
initiated manually when the supply fan status is OFF. (HOA
switch is in OFF position.) In order to reactivate all
the configured control routines, press

and then press

.

Timed Override (39) — Indicates that the unit operation has
been extended by the user. Unit must be configured for

Timed Override schedule and timed override hours (

).

Table 14 — Display Codes

FORCE STATES

Display

Description

1

Fire mode force

2

Internal safety force

3

Quick Test/Service tool force

4

HSIO/Building Supervisor force

5

Remote Building Supervisor force

6

Loadshed minimum offtime force

7

Data transfer force

8

BEST (Building Environmental Systems
Translator) force

9

Temperature override force

10

Loadshed force

OPERATING MODES

Display

Description

21

Temperature Reset in effect

22

Demand Limit in effect

23

Unoccupied Heating mode

24

Unoccupied Cooling mode

26

Optimal Start mode

27

Unoccupied mode

29

Optimal Stop mode

30

Occupied Heating mode

31

Occupied Cooling mode

32

Occupied Fan Only mode

33

Nighttime Free Cooling mode

34

Pressurization mode

35

Evacuation mode

36

Smoke Purge mode

37

Fire Shutdown mode

38

Quick Test mode

39

Timed Override mode

ALARMS

Display

Description

60

Air quality 1 high limit

61

Air quality 2 high limit

62

Air quality/constant outside air suspended

63

(Not used)

64

DX cooling shutdown

65

Pressurization

66

Evacuation

67

Smoke purge

68

Fire shutdown

69

Service/maintenance required

70

Linkage failure

71

Space temperature low limit

72

Space temperature high limit

73

Supply-air temperature low limit

74

Supply-air temperature high limit

75

Return-air temperature low limit

76

Return-air temperature high limit

77

Mixed-air temperature low limit

78

Mixed-air temperature high limit

79

Outside-air temperature low limit

80

Outside-air temperature high limit

81

Static pressure low limit

82

Static pressure high limit

83

Relative humidity low limit

84

Relative humidity high limit

85

Fan status

86

Freezestat

87

Analog temperature control sensor low limit

88

Analog temperature control sensor high limit

89

Outside-air relative humidity low limit

90

Outside-air relative humidity high limit

91

Supply velocity pressure low limit

92

Supply velocity pressure high limit

93

Return velocity pressure low limit

94

Return velocity pressure high limit

95

Delta CCFM low limit

96

Delta CCFM high limit

97

Filter status

98

Duct high humidity

CCFM — Cfm x 100

79