— Used to verify software version.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

— Used to verify and change factory configura-

tion. Requires password entry in

. See Example 7.

NOTE: When more than one unit is connected to the
Carrier Comfort Network, the element address must be changed
on all but one unit. The element address system default
is 1, and element address numbers cannot be repeated.
Element address must be changed at the local interface
device.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Example 7 — Reading and Changing

Factory Configurations

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS

FACT CFG

Factory configuration sub-
function of service function

TYPE CV

Unit type is constant volume

UNIT TYPE IS CV

Explanation is scrolled across
screen

TYPE VAV

Unit type is changed to VAV

COOL COI

Cooling type is coil

DXST 2

DX cooling stage quantity is 2

HEAT HCL

Heating type is hot water/
steam coil

HEAT NON

Changed to no heat unit

HEAT ELE

Changed to electric heat

HEAT COI

Heating type is changed back
to hot water/steam coil

EHST 0

Electric heater stages = 0

EHST N

Electric heater stages = N,
where N = number of stages

MIXD ALG

Unit with mixed air dampers

MIXD NON

Changed to without dampers

IAQT 1

Indoor air quality type
is single gas sensor

MATP YES

Mixed air temperature
protection enabled

BUS 0

Bus number = 0

ADR 1

Element address = 1

ADR 2

Element address changed to 2

PSW XXXX

Password

— Used to change the HSIO display of the measure-

ments from English to Metric. See Example 8.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

— Used to read or change factory configuration of

user options. See Example 9.

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Example 8 — Configuration of Measurements

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS

UNIT 0

Measurements are displayed using
English (0 = English, 1 = Metric)

UNIT 1

Measurements are now displayed
using the Metric system

UNIT 0

Measurements are returned to
English

Example 9 — User Configurations

KEYBOARD

ENTRY

DISPLAY

RESPONSE

COMMENTS

USER CFG

User configurations

NTEN DSB

NTFC is disabled

NTEN EN

NTFC is enabled

NTEN DSB

NTFC is disabled

HUEN 0

Humidifier control is none

HUEN 1

Unit changed to analog humidifier
control

HUEN 0

Humidifier control is changed back
to none

OHEN DSB

Scroll past occupied heating
(disabled)

RSEN DSB

Space temperature reset (disabled)

DLEN DSB

Scroll past demand limiting
(disabled)

FTEN DSB

Fan tracking (disabled)

OAEN DSB

Constant outside air (disabled)

NPEN DSB

Night purge (disabled)

AQEN DSB

Indoor air quality (disabled)

IAQP DSB

Indoor air quality priority
level (disabled)

OSEN DSB

Optimal start is disabled

OSEN EN

Optimal start is enabled

OSEN DSB

Optimal start is disabled

TSCH 1

Time schedule No. 1 is enabled

TSCH 2

Time schedule No. 2 is enabled

TSCH 1

Time schedule is changed back to
No. 2

TOVR 0

Time override value = 0 hrs

TOVR 1

Time override value = 1 hr

TOVR 0

Time override value = 0 hrs

NTFC — Nighttime Free Cooling