Carrier 39L User Manual
Page 84
— Used to verify software version.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
— Used to verify and change factory configura-
tion. Requires password entry in
. See Example 7.
NOTE: When more than one unit is connected to the
Carrier Comfort Network, the element address must be changed
on all but one unit. The element address system default
is 1, and element address numbers cannot be repeated.
Element address must be changed at the local interface
device.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Example 7 — Reading and Changing
Factory Configurations
KEYBOARD
ENTRY
DISPLAY
RESPONSE
COMMENTS
FACT CFG
Factory configuration sub-
function of service function
TYPE CV
Unit type is constant volume
UNIT TYPE IS CV
Explanation is scrolled across
screen
TYPE VAV
Unit type is changed to VAV
COOL COI
Cooling type is coil
DXST 2
DX cooling stage quantity is 2
HEAT HCL
Heating type is hot water/
steam coil
HEAT NON
Changed to no heat unit
HEAT ELE
Changed to electric heat
HEAT COI
Heating type is changed back
to hot water/steam coil
EHST 0
Electric heater stages = 0
EHST N
Electric heater stages = N,
where N = number of stages
MIXD ALG
Unit with mixed air dampers
MIXD NON
Changed to without dampers
IAQT 1
Indoor air quality type
is single gas sensor
MATP YES
Mixed air temperature
protection enabled
BUS 0
Bus number = 0
ADR 1
Element address = 1
ADR 2
Element address changed to 2
PSW XXXX
Password
— Used to change the HSIO display of the measure-
ments from English to Metric. See Example 8.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
— Used to read or change factory configuration of
user options. See Example 9.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Example 8 — Configuration of Measurements
KEYBOARD
ENTRY
DISPLAY
RESPONSE
COMMENTS
UNIT 0
Measurements are displayed using
English (0 = English, 1 = Metric)
UNIT 1
Measurements are now displayed
using the Metric system
UNIT 0
Measurements are returned to
English
Example 9 — User Configurations
KEYBOARD
ENTRY
DISPLAY
RESPONSE
COMMENTS
USER CFG
User configurations
NTEN DSB
NTFC is disabled
NTEN EN
NTFC is enabled
NTEN DSB
NTFC is disabled
HUEN 0
Humidifier control is none
HUEN 1
Unit changed to analog humidifier
control
HUEN 0
Humidifier control is changed back
to none
OHEN DSB
Scroll past occupied heating
(disabled)
RSEN DSB
Space temperature reset (disabled)
DLEN DSB
Scroll past demand limiting
(disabled)
FTEN DSB
Fan tracking (disabled)
OAEN DSB
Constant outside air (disabled)
NPEN DSB
Night purge (disabled)
AQEN DSB
Indoor air quality (disabled)
IAQP DSB
Indoor air quality priority
level (disabled)
OSEN DSB
Optimal start is disabled
OSEN EN
Optimal start is enabled
OSEN DSB
Optimal start is disabled
TSCH 1
Time schedule No. 1 is enabled
TSCH 2
Time schedule No. 2 is enabled
TSCH 1
Time schedule is changed back to
No. 2
TOVR 0
Time override value = 0 hrs
TOVR 1
Time override value = 1 hr
TOVR 0
Time override value = 0 hrs
NTFC — Nighttime Free Cooling