Error message and related information
Relevant
LED displays
Meaning of the error and
countermeasures
Error message
information
1
Information
2
information
3
special
relay
RUN
FAULT
I/O
Program
No sub-r entry
Program
type-
Block No.
Address
in the
block
Subroutine
No.
S0006
S0030
O
•
O
The "SUBR" instruction of the subroutine
No. specified by the "CALL" instruction is
not programmed. Insert the "SUBR"
instruction.
No RET error
Program
type-
Biock No.
Address
in the
biock
Subroutine
No.
S0006
S0030
o
•
0
The "RET" instruction is not programmed
in the subroutine.
Insert the “RET" instruction.
Sub-r nesting err
Program
type-
Btock No.
Address
in the
biock
Subroutine
No.
S0006
S0030
O
•
o
The number of nesting of subroutines
exceeds six overlays.
Change the program to reduce the number
of nesting overlays to six or fev^rer.
Loop nesting error
Program
type-
Block No.
Address
In the
block
S0006
S0030
o
•
0
The number of nestings of "FOR" and
"NEXT" instructions exceed six overlays.
Reduce the number of overlays of the
"FOR" and "NEXF instructions to six or
fewer in the program.
SFC step No. error
Program
type-
Block No.
Step No.
S0006
S0030
o
•
o
Step No. is duplicated in the SFC program,
or the step Nos. specified by the initial step
and the end step are not identical. Change
the step No., or check the step No. of the
end step.
SFC macro No. err
Program
type-
Biock No.
Macro No.
S0006
S0030
o
•
o
Macro No. is duplicated, or the same
macro program is called from two or more
locations.
Change the macro No. Or, limit the catling
of the macro program to one location.