Toshiba Programmable Controller PROSEC T3 User Manual
Page 95
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

c
w
(D
T.
w
3
u
a
i
3
09
-M
Part
Error message and related Information
Relevant
LED displays
Meaning of the error and
countermeasures
Error message
Information
1
Information
2
Information
3
special
relay
RUN
FAULT
I/o
I/O
Invalid I/O intrpt
Unit No. -
Slot No.
S0005
S0025
A request for I/O interrupt from an interrupt
module not registered has been detected
(No error-down occurs).
Register the interrupt module, or do not
mount that interrupt module.
Duplicate I/O reg
Unit No. -
Slot No.
Register
No.
S0005
S0021
O
•
•
An overlap is detected in allocating I/O
registers to I/O modules. Correct the I/O
allocation Information.
Illegal I/O reg
Unit No. -
Slot No.
Register
No.
S0005
S0021
o
•
•
The allocation of I/O modules to I/O
registers has exceeded the limit. Reduce
the number of allocations to I/O modules.
Proc
essing
LP function error
Error code
Error data
S0004
S0015
o
•
o
An abnormality is detected in the language
processor (LP).
If the abnormality remains after power
cycle, replace the CPU module.
LP reg FVW error
Port No.
Error data
Test data
S0004
S0015
o
•
o
At initial setting of the language processor
(LP), an abnormality has occurred in the
read/write checking. If the abnormality
remains after power cycle, replace the
CPU module.
LP exec timeout
S0004
S0015
o
•
o
The execution of the language processor
(LP) did not finish within a time specified.
Reduce the program execution time or use
the "WOr instruction.
If the situation is repeated after power
cycle, replace the CPU module.
Scan time over
Scan time
S0006
S0031
o
•
O
The scan time exceeded 200 ms.
Reduce the scan time or use the "WDT"
instruction.
O)
H
o
c
2
(D
(n
D"
O
O
(O