1. System Configuration
1.8
List of I/O Modules
This manual explains the basic I/O modules in the list below and
how to use them.
Type
Specification
DI334
DC
input
32 points (8 pts common), 12 to 24 Vdc,
10 mA/point
DI334H
32 points (8 pts common), 12 to 24 Vdc,
10 mA/point, high-speed response
D1335
64 points (8 pts common), 24 Vdc,
5 mA/point
DI335H
64 points (8 pts common), 24 Vdc,
5 mA/point, high-speed response
IN354
AC
input
32 points (8 pts common), 100 to 120 Vac,
10 mA/point
IN364
32 points (8 pts common), 200 to 240 Vac,
10 mA/point
D0333
DC
output
16 points (8 pts common), 12 to 24 Vdc,
2 A/point, 5 A/common
D0334
32 points (16 pts common), 12 to 24 Vac,
0.5 A/point, 5 A/common
D0335
64 points (8 pts common), 5 to 24 Vdc,
100 mA/point
AC363
AC
output
16 points (8 pts common), 100 to 240 Vac,
2 Appoint, 5 A/common
AC364
32 points (16 pts common), 100 to 240 Vac,
0.5 A/point, 3.2 A/common, 5 A/module
R0364
Relay
output
32 points (8 pts common), 240 Vac/24 Vdc,
2 A/point, 5 A/common
R0363S
16 points (isolated contact), 240 Vac/24 Vdc,
2 A/point
For details on the specification of I/O modules, see 2.3, I/O
module specifications.
Carefully read the Cautions described In Section 3 for applying
I/O modules.
The I/O module can be mounted in any I/O slot functionally.
However, to improve noise-immunity for the entire system, it is
recommended to separate the low voltage 1/Os and the power
I/Os. (See 4.7, I/O Wiring.)
22
PROSEC T3