E8 Controller and BCM for Modulex EXT

Installation, Operation & Maintenance Manual

CHAPTER 8: BOILER COMMUNICATION MODULE (BCM)

Page

90 of 108

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0093_0A

PRI: 06/24/2013

Phone: 800-526-0288

GF-136-C

start level percentage (programmed by the user into the BMS II/ACS), the BMS II/ACS will call

on the second boiler to begin firing one module, and the BMS II/ACS will then split the fire rate

signal between the two boilers and send each a signal equal to the start level

percentage. When the combined BMS II/ACS fire rate signal to the two boilers reaches a value

three times that of the start level percentage, the BMS II/ACS will call on the third boiler to begin

firing one module, and the BMS II/ACS will then split the fire rate signal between the three

boilers and send each a signal equal to the start level percentage. As the demand increases, in

a similar method as above, the BMS II/ACS will call on the BCM of the fourth boiler to turn on

one module. At this point, the BMS II will modulate the fire rate signal to the boilers in a parallel

manner, while the BCM of each boiler sequences the individual modules.
Boiler inputs will modulate down and come off line in response to the BMS II/ACS in a reverse

manner. Whether the BMS II/ACS is set in a Constant Temperature or Modulating Temperature

mode, it will use the modulating ability to prevent header temperature fluctuation and maximize

efficiency. As well, the BMS II/ACS can stage auxiliary equipment such as combustion air

dampers and fans. Refer to BMS II Operations and Maintenance Manual GF-124/ACS Manual

GF-131, and Product Spec BMS-II for details.