beautypg.com

1 bcm fault relay wiring, 2 clearing faults, 3 bcm configured as back-up controller – AERCO Modulex E8 Controller (and BCM) For Modulex EXT Boilers User Manual

Page 80: 1 bcm back-up controller wiring, E8 controller and bcm for modulex ext

background image

E8 Controller and BCM for Modulex EXT

Installation, Operation & Maintenance Manual

CHAPTER 8: BOILER COMMUNICATION MODULE (BCM)

Page

80 of 108

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0093_0A

PRI: 06/24/2013

Phone: 800-526-0288

GF-136-C

8.2.1 BCM Fault Relay Wiring

If desired, pins 3 and 4 of connector Y4 (Figure 8-3) can be wired to an external source to

provide a remote alarm indication when the BCM Fault Relay is activated.

8.2.2 Clearing Faults

A fault can be cleared by pressing and releasing the black Reset Switch on the front cover of

the BCM. However, if the cause of the fault has not been corrected, the Fault Relay will again

be activated.

Figure 8-3: BCM Fault Relay & Reset Switch Wiring

8.3 BCM Configured as Back-Up Controller

When the BCM is configured as the Back-Up Controller for the E8, it will assume control of the

Modulex Boiler if the E8 fails. In the event of an E8 Controller failure, the BCM will operate the

Modulex Boiler in the Constant Setpoint Mode (default setpoint = 180°F [82°C]). The primary

Boiler Pump must also be wired to the BCM so it will run when the BCM assumes control in the

Back-Up Mode.
If a setpoint temperature lower than 180°F is desired, the setpoint can be changed prior to boiler

start-up. Refer to Section 8.3.1 for details.

8.3.1 BCM Back-Up Controller Wiring

The Primary Boiler Pump must be wired to BCM Connector Y4 as shown in Figure 8-4. Also, if

a Constant Setpoint temperature lower than the default setting of 180°F (82°C) is desired in the

event of an E8 failure, the appropriate resistor must be connected across terminals 6 and 7 of

BCM Connector Y2 as shown in Figure 8-5.