CHAPTER 8: BOILER COMMUNICATION MODULE (BCM)

OMM-0093_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page

79 of 108

GF-136-C

Ph.: 800-526-0288

PRI: 06/24/2013

The BCM Change-Over Series/Parallel 3-Position Switch and the Enable/Disable (I/0) 2-

Position Switch function as described in Table 8-1.

Table 8-1: Two and Three Position Switch functions

2-POSITION

SWITCH

(BCM Backup)

O

(OFF / DISABLED)

(To NOT use BCM

as backup)

I

(ON \ ENABLED)

(To use BCM as

backup)

3-POSITION

SWITCH

(Internal/External Boiler Control)

I

(NOTE 1)

O

(NOTE 2)

II

(NOTE 3)

DO

NOT

USE

The BCM is the Gate-way

for Modbus and external

control. The E8 does

not

control the boiler and the

BCM will

NOT take over the

boiler if the Modbus signal

fails.

The E8

is the primary

controller and the BCM

allows monitoring through

Modbus, but will

NOT take

over boiler if the E8 fails.

DO

NOT

USE

The BCM is the Gate-way

for Modbus and external

control. The E8 does

not

control the boiler and the

BCM

WILL take over the

boiler if the Modbus signal

fails. If E8 is in Standby

Mode, BCM will cycle the

pump with the boiler. If E8

is in Day Mode, the E8 will

continuously run the pump.

The E8

is the primary

controller and the BCM

allows monitoring, and the

BCM

WILL take over the

boiler if E8 fails. If E8 is in

Standby Mode, E8 will cycle

the pump (must use

Enable/Disable). If E8 is in

Day Mode, the E8 will

continuously run the pump.

NOTE 1

DO NOT set the 3-Position Switch to Position I.

NOTE 2

Set the 3-Position Switch to Position O ONLY when controlling

Boilers from an external Controller via Modbus Communication.

See Section 3.1.2 for setting HEAT Modes.

NOTE 3

Position II is the Default position for the 3-Position Switch. Ensure

it is set to this position when it arrives from the Factory. See

Section 3.1.2 for setting HEAT Modes.

8.2 BCM Fault Relay

The BCM Fault Relay is activated (energized) when a fault condition occurs in the Modulex

Boiler. When activated, the Fault Relay provides contact closure across pins 3 and 4 of

connector Y4 on the BCM board. In addition, the red LED on the BCM board will light

continuously.