E8 controller and bcm for modulex ext – AERCO Modulex E8 Controller (and BCM) For Modulex EXT Boilers User Manual
Page 43

E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS
OMM-0093_0A
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page
43 of 108
GF-136-C
Ph.: 800-526-0288
PRI: 06/24/2013
Table 5-4: EXPERT Menu Listing (Continued)
FUNCTION
DESCRIPTION
ENTRY
RANGE
DEFAULT
INSTALLATION Sub-Menu (Continued)
SEQU CHANGE
Sequence change mode
01 – 06
06
SEQ SW TIME
Time to sequence change (hours)
10 – 800
200
LOCK TIME
Not Applicable
00 min – 30 min
00
HYST BURNER2
Not Applicable
----
----
HS COOL-FCT
Not Applicable
----
----
T-HS COOL
Not Applicable
----
----
HEATSOURCE 1
Identification of Boiler Type being used:
00 = No Boiler
01 = Single-Stage, switching
02 = Single-Stage, modulating
03 = 2-Stage, switching
04 = 2 individual, switching
05 = Multi-Stage, switching
06 = Multi-Stage, modulating (cascade via BUS)
See
DESCRIPTION
06
(Multi-Stage
Modulating)
HS 1 BUS
Communication connection between Controller and
Heat Source
00 – 04
02
HEATSOURCE 2
Not Applicable
N/A
N/A
STORAGE HS2
Not Applicable
N/A
N/A
BUFFER
Not Applicable
N/A
N/A
SCREED
Not Applicable
N/A
N/A
SCREED PROGR Not Applicable
N/A
N/A
RETURN
Press Program Key to exit INSTALLATION Sub-Menu.
HOT WATER Sub-Menu
DHW RELIEF
Not Applicable
N/A
N/A
PARALLEL
Parallel pump operation.
00 = Hot Water Priority
01 = Hot Water Partial Priority
02 = Pump Parallel Running
00, 01, 02
01
T-BOILER DHW
Boiler temperature increase during Hot Water
operation.
Boiler Temp = (DHW Temp Setting) + (T-BOILER
DHW)
32°F – 194°F
97°F
HYST DHW
Hot Water Hysteresis
48°F – 129°F
48°F
DHW FOLLOWUP Pump Run-Down Time
00 min. – 30
min.
00 min.
THERM INPUT
Storage Tank With Sensor = 00
Storage Tank With Thermostat = 01
00, 01
00 (Off)
WALL HUNG
Not Applicable
00 (Off)
LOAD THROUGH Not Applicable
00 (Off)
RETURN
Press Program Key to exit HOT WATER Sub-Menu.
EXPERT
EXPERT