beautypg.com

5 bcm control of vfd primary pump, 1 pump control wiring, 2 pump control operation – AERCO Modulex E8 Controller (and BCM) For Modulex EXT Boilers User Manual

Page 84: 6 rs485 loop termination resistors and bias, E8 controller and bcm for modulex ext

background image

E8 Controller and BCM for Modulex EXT

Installation, Operation & Maintenance Manual

CHAPTER 8: BOILER COMMUNICATION MODULE (BCM)

Page

84 of 108

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0093_0A

PRI: 06/24/2013

Phone: 800-526-0288

GF-136-C

8.4.4 AERCO BMS II/ACS Master to BCM Slave Wiring Connections.

The AERCO BMS II/ACS contains a RS232 port for connection to an EMS/BAS or personal

computer. In addition, the BMS II/ACS contains a RS485 port for connection to the BCM’s

Modbus input.

8.4.5 EMS or BAS Master to BCM Slave Wiring Connections

When a third-party EMS or BAS Master is used, the Modbus Network connections will depend

on the available communication port(s) on the EMS/BAS. Many EMS/BAS Models contain only

a RS232 (DB9) port, while others contain either a 2-Wire or 4-Wire RS485 port. In addition,

some EMS/BAS models contain both a RS232 and a RS485 port. If the EMS or BAS is

equipped with only a RS232 port, a RS232-to-RS485 converter will be required (such as a B&B

Electronics, Model 485SD9TD or AERCO Part No. 124943).

8.5 BCM Control of VFD Primary Pump

The BCM has a 0-10 V output that can be used to control a VFD primary pump. There is no

connection on the Modulex controller for pump mains power. Pump mains power must be

supplied externally, as directed by pump manufacturer’s instructions.

8.5.1 Pump Control Wiring

The 0-10 V signal wire must be wired to terminals 5 and 6 of terminal block Y2. See Figure 8-8.

The positive wire connects to terminal 5 and the negative to terminal 6.

8.5.2 Pump Control Operation

Adjustment of the 0-10 V signal is done through 3 Modbus registers. For setup and operation of

Modbus controls see Sections 8.7, 8.8, and 8.9. Data address 3006 is the “Pump Over-run

Time” and it controls the amount of time, in minutes, that the pump will continue to run after the

unit is shut down. Addresses 3007 and 3008 control the output voltage at minimum and

maximum fire, respectively. For further information see Table 9-4.

Figure 8-8: Primary Pump Control Wiring to BCM

8.6 RS485 Loop Termination Resistors and Bias

A terminating resistor (120 ohms) on each end of the RS485 loop is designed to match the

electrical impedance characteristic of the twisted-pair loop and prevent echoes or cross-talk

from corrupting data on the line. Short or medium length Modbus/RS485 loops (less than 1000