E8 Controller and BCM for Modulex EXT

Installation, Operation & Maintenance Manual

CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS

OMM-0093_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page

53 of 108

GF-136-C

Ph.: 800-526-0288

PRI: 06/24/2013

5.7 Installation Menu & E8 Controller Initial Startup

See Section 4.1 for instructions for initial startup of the E8 Controller, which requires a number

of one-time entries to be made in the initial INSTALLATION Menu that appear in the E8

display when the controller door is first opened. Table 5-8 lists the description, entry range,

and default entry for all INSTALLATION MENU parameters.

Table 5-8: INSTALLATION Menu Listing

PARAMETERS

DESCRIPTION

ENTRY

RANGE

DEFAULT

INSTALLATION Sub-Menu
LANGUAGE

Set Language

ENGLISH

TIME

Set current time (min., hrs)

00:00 – 24:00

YEAR

Set current year

XXXX (4

digits)

MONTH

Set current month

00-12

DAY

Set current day of month

00-31

CONF DEVICE

Confirm Device

- - - -, 01 – 06

- - - -

HEATSOURCE 1 Heat Source 1

00 – 06

06

HS1 BUS

Heat Source 1 Bus

00 – 04

02

HEATSOURCE 2

Heat Source 2

00 – 05

00

STORAGE HS2

Storage Heat Source 2

00 – 03

00

BUFFER

Buffer

00, 01, 02

00

HC FUNCTION 1

Heating Circuit Function 1

00, 01, 03

00

HC FUNCTION 2

Heating Circuit Function 2

00 – 04

00

CAP/MODULE

See Section 5.7.1 for instructions.

00 – 1000 Kw

40 Kw

RELAY FUNC 1

Relay Function 1 (See Section 5.7.2)

00 – 26

00

T-MF1 SETP

Temperature – Multifunction Relay 1 Setpoint

86°F – 194°F

86°F

MF1 HYST

Multifunction Relay 1 Hysteresis

4°F – 18°F

9°F

RELAY FUNC 2

Relay Function 2 (See Section 5.7.2)

00 – 26

00

T-MF2 SETP

Temperature – Multifunction Relay 2 Setpoint

86°F – 194°F

86°F

MF2 HYST

Multifunction Relay 2 Hysteresis

4°Ra – 18°Ra

9°F

RELAY FUNC 3

Relay Function 3

00 – 26

01

T-MF3 SETP

Temperature – Multifunction Relay 3 Setpoint

86°F – 194°F

86°F

MF3 HYST

Multifunction Relay 3 Hysteresis

4°F – 18°F

9°F

RELAY FUNC 4

Relay Function 4

00 – 26

02

T-MF4 SETP

Temperature – Multifunction Relay 4 Setpoint

86°F – 194°F

86°F

MF4 HYST

Multifunction Relay 4 Hysteresis

4°F – 18°F

9°F

BUS ID 1

Bus Identification No. 1

00 – 15

01

BUS ID 2

Bus Identification 2

00 – 15

02

5K SENSOR

5,000 Ohm Sensor

00=5K,

01=1K

00 = 5 K

INSTALL

INSTALL