beautypg.com

3 bcm fault code table, E8 controller and bcm for modulex ext – AERCO Modulex E8 Controller (and BCM) For Modulex EXT Boilers User Manual

Page 104

background image

E8 Controller and BCM for Modulex EXT

Installation, Operation & Maintenance Manual

CHAPTER 10: E8, BCM, AND BMM FAULT CODES

Page

104 of 108

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0093_0A

PRI: 06/24/2013

Phone: 800-526-0288

GF-136-C

10.2.3 BCM Fault Code Table

The table below lists the fault codes and troubleshooting tips associated with the BCM.

Table 10-3: BCM Fault Codes

CODE

DESCRIPTION

EFFECT

CORRECTION

RESET

17

Boiler Pipe is frozen.

FlowSensor temp. is

36°F or less.

Ignition is

inhibited. Pump

runs for 5 min at

max speed.

Carefully defrost

boiler

AUTOMATIC - when

FlowSensor is greater than

41°F.

18

Maximum Δ-

temperature

protection. Flow

temperature - Return

Temperature > Water

Δ-Temp Protection +

50°F

All burners

turned OFF and

Pump ON at

maximum speed.

Check the

system

installation.

AUTOMATIC - when Δ-

temperature < Water Δ-

Temp Protection.

19

High outlet

temperature.

FlowSensor

temperature > 203°F.

All burners

turned OFF and

Pump ON at

maximum speed.

Check Flow

Sensor or

system pump

AUTOMATIC - when

FlowSensor < 176°F.

37

Crash

Ignition is

inhibited

Change the

BCM

MANUAL – push reset

switch to cycle power

38

Settings Corrupted

Ignition is

inhibited. Pump

runs for 5 min at

max speed.

Re-program the

settings.

Contact Factory

MANUAL - push reset

switch or cycle power.

50

Internal Failure

Ignition is

inhibited.

Contact Factory

for new BCM.

MANUAL - cycle the

power.

56

Standby. No remote

control detected and

Request input is open.

Ignition is

inhibited.

Close Request

input for Manual

operation.

MANUAL - push reset

switch or cycle power.

57

No BMM detected.

Ignition is not

possible.

Check the BMM

eBus wiring.

MANUAL - push reset

switch or cycle power.

58

FlowSensor fault.

All burners

turned OFF.

Check flow

sensor or wiring. AUTOMATIC