E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS
Page
42 of 108
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0093_0A
PRI: 06/24/2013
Phone: 800-526-0288
GF-136-C
Table 5-4: EXPERT Menu Listing (Continued)
FUNCTION
DESCRIPTION
ENTRY
RANGE
DEFAULT
INSTALLATION Sub-Menu (Continued)
HYSTERESIS Not Applicable
----
----
FOUND
MODULS
Displays the number of heat modules available
for service.
Display
CAP/MODULE Displays the maximum Kw output of each heat
module.
00 – 1000 Kw
50 Kw: 321-1123
110 Kw: 1530-3060
NEW CONFIG Not Applicable
----
----
MIN MOD
CASC
Not Applicable
01 – 08
01
HW-BOILER
Not Applicable
00 – 08
00
CONTR
DEVIAT
Control Deviation indicates the temperature
difference between the Boiler set point and the
actual water temperature.
Display
----
DES OUPUT
Required system output [in %]
0 – 100%
00
SWITCH TIME Not Applicable
(N/A)
(N/A)
BLOCK TIME
Not Applicable
(N/A)
(N/A)
MAX T-
MODUL
Maximum temperature of Heat Module
122.0°F to
230.0°F
194.0°F
DYN
UPWARD
Not Applicable
(N/A)
(N/A)
DYN
DOWNWARD Not Applicable
(N/A)
(N/A)
RESET TIME
Not Applicable
5 – 500
50
MODULAT
MAX
Start Level. If this modulation percentage is
exceeded, the next heat module is connected
after the delay time elapses.
50% - 100%
30%
MODULAT
MIN
Stop Level. If value drops below this
modulation percentage, the last heat generator
(module) of the current sequence is switched
off
10% - 60%
35%
MIN MOD HS Not Applicable
0% - 60%
35%
MOD LEVEL
HW
Not Applicable
----
----
SEQUENCE 1 Boiler sequence 1
12345678
SEQUENCE 2 Boiler sequence 2
87654321
EXPERT
EXPERT