beautypg.com

8 modbus software set-up, 1 bcm set-up for modbus operation, 2 monitoring and configuration only – AERCO Modulex E8 Controller (and BCM) For Modulex EXT Boilers User Manual

Page 88: E8 controller and bcm for modulex ext

background image

E8 Controller and BCM for Modulex EXT

Installation, Operation & Maintenance Manual

CHAPTER 8: BOILER COMMUNICATION MODULE (BCM)

Page

88 of 108

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0093_0A

PRI: 06/24/2013

Phone: 800-526-0288

GF-136-C

8.8 Modbus Software Set-Up

The following sections provide the information and procedures necessary to configure the Boiler

Communications Modules (BCMs) to operate on a Modbus Network.

8.8.1 BCM Set-Up For Modbus Operation

The BCM Controller can be set up for the following types of Modbus operating modes:

Monitoring and Configuration Only

AERCO BMS II/ACS Modbus Control and Monitoring

Modbus Remote Setpoint Control and Monitoring

In order for the BCM Controller to be recognized by the Modbus Master, a valid address must

be set at each BCM on the Modbus Network. Address selection on each BCM is accomplished

by setting rotary DIP switch SW1. This switch is located in the lower right portion of each BCM

as shown in Figure 8-12.
SW1 is a 10-position switch labeled 0 – 9 (Figure 8-12). SW1 is set to the desired position using

a small flat-tip screwdriver. Figure 8-12 shows SW1 set to address 0 (zero) which disables the

BCM on the Modbus Network. Only Modbus addresses 1 through 9 will be recognized by the

Modbus Master. SW1 must be set to a different position for each Modulex Boiler being

controlled on the Modbus Network.
Once the desired address has been set on each BCM, the Modulex Boiler is configured for

Modbus Network control by the controlling Master EMS/BAS or AERCO BMS II/ACS. In order

for the BCM to act as the Back-Up Controller if the Modbus Master signal is lost, the

ENABLE/DISABLE switch must be set to ENABLE (1).
See Chapter 9 of this document and Chapter 2 of GF-124 for Modbus points for the BCM and

BMS II/ACS.

Figure 8-12: Location of BCM Address Selection Switch SW1

8.8.2 Monitoring and Configuration Only

For monitoring and configuration only, set the 3-position switch to position II when the E8 is

controlling the boiler. The boiler operation can be monitored via the Modbus terminals.