Troubleshooting
89
If the EPI server has failed:
4.
Switch the server AB changeover switch to the backup position.
5.
Power down the failed EPI server.
6.
Power up the backup EPI server.
7.
Double click EPI Refresh on each Fusion VRC or HDVRC computer in the
Fusion system that will connect to this EPI server.
After a few seconds delay while the EPI server boots up and establishes
connections, all Autocam heads should be online and available (white
buttons).
Fig. 56 EPI refresh
NOTE: Refer to the VRC Technical Guide (publication no. V4009-4990) for
instructions on creating the EPI Refresh shortcut, if it is not on the VRC
desktop.
EPI Refresh