Configuration

39

Figure 20. Edit Advanced Shutdown Criteria Dialog Box

Criteria Definition

Shutdown criteria is reached (enabled by default): This is the standard shutdown sequence taking into

account “time based criteria” and “UPS low battery level criteria.”

Fault Alarms

You can also select one or several events in the following events list. If these events are selected, they will

trigger an immediate shutdown in the order in which they occur:

• UPS Fault (internal fault or battery fault)
• UPS Overload
• Output on bypass
• Communication failure

NOTE:

When using a Virtual Power Source (in a redundant configuration), only the following criteria can be used:

Shutdown criteria is reached, Redundancy Lost, and Protection Lost.

Edit UPS Configuration

To edit the UPS configuration:

1 Login with an administrator user profile.
2 Select Settings > Shutdown. The Shutdown page is displayed.
3 Click Edit UPS configuration. The Edit UPS Configuration dialog box displays (see Figure 21).
4 Change parameters as needed.