MMD-TA-11B / MMD-TA-12B Muting Module

Instruction Manual

System Installation

Figure 3-27. Generic machine interface hookup, model

MMD-TA-11B: MPCE with 2-channel EDM

Figure 3-28. Generic machine interface hookup, model

MMD-TA-11B: MPCE with 1-channel EDM

A1

+24V dc

0V dc

EDM1

EDM2

L2

L1

K1A

K2A

K1B

K1C

K2B

K2C

MMD-TA-11B

A2

Y1

Y2

Y3

Y4

32

23

24

31

14

MPCE1

13

Machine
Control
Circuits

MPCE2

A1

+24V dc

0V dc

EDM1

EDM2

L2

L1

K1A

K2A

K1B

K1C

K2B

K2C

MMD-TA-11B

A2

Y1

Y2

Y3

Y4

32

23

24

31

14

MPCE1

13

Machine
Control
Circuits

MPCE2

WARNING . . .

Proper Wiring

The generalized wiring configurations shown
are provided only to illustrate the importance of

proper installation. The proper wiring of the Muting Module to
any particular machine is solely the responsibility of the
installer and end user.

CAUTION . . .

Shock Hazard

Always disconnect all power from the Muting
Module and the guarded machine before

making any connections or replacing any component.
Use extreme caution to avoid electrical shock at all times.
Serious bodily injury or death could result.

WARNING . . .

Use of Transient

Suppressors

Transient suppressors are recommended.

They MUST be installed across the coils of the machine
control elements. NEVER install suppressors directly
across the outputs of the Module! It is possible for
suppressors to fail as a short circuit. If installed directly
across the contacts of the Module, a short-circuited
suppressor will create an unsafe condition.