beautypg.com

System installation, Warning, 2 muting devices – Banner MMD-TA-11B Muting Modules User Manual

Page 20

background image

18

P/N 116390 rev. C

Banner Engineering Corp.

Minneapolis, U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

MMD-TA-11B / MMD-TA-12B Muting Module

Instruction Manual

System Installation

WARNING . . .

Avoid Hazardous

Installations

Two or four independent position switches (at

M1–M2 or M3–M4) must be properly adjusted or positioned
so that they close only after the hazard no longer exists,
and open again when the cycle is complete or the hazard
is again present. If improperly adjusted or positioned,
injury or death could result.
The user has the responsibility to satisfy all local, state, and
national laws, rules codes, and regulations relating to the use
of safety equipment in any particular application. It is extremely
important to be sure that all appropriate agency requirements
have been met and that all installation and maintenance
instructons contained in the appropriate manuals are followed.

3.5.2 Muting Devices

The user is required by OSHA and ANSI to arrange, install,

and operate the safety system so as to protect personnel and

minimize the possibility of defeating the safeguard.
Mute devices must meet a 3-second simultaneity requirement to

activate muting; that is, devices in a pair must be activated within

3 seconds of one another.

General Muting Device Requirements

The muting devices (typically sensors or switches) must, at a

minimum, comply with the following requirements:
1. There must be a minimum of two independent hard-wired

muting devices.

2. The muting devices must either both have normally open

contacts; or one device with a PNP output and one device

with a NPN output, both of which must fulfill the input

requirements listed in the Specifications (Section 2). These

contacts must close when the switch is actuated, and must

open (or not conduct) when the switch is not actuated or in a

power OFF condition.

3. The activation of the inputs to the muting function must be

from separate sources. These sources must be mounted

separately in order to prevent an unsafe muting condition

resulting from misadjustment, misalignment, or a single

common mode failure. (For example, physical damage to

the mounting surface could cause both muting devices to

be knocked out of alignment, resulting in false muting input

signals.) Only one of these sources may pass through, or be

affected by, a programmable logic controller or similar device.

4. The muting devices must be installed so that they can not be

easily defeated or bypassed.

5. The muting devices must be mounted so that their physical

position and alignment can not be easily changed.

6. It must not be possible for environmental conditions to initiate

a mute condition (e.g., extreme airborne contamination).

7. The muting devices must not be set to use any delay or other

timing functions (unless such functions are accomplished so

that no single component failure prevents the removal of the

hazard, subsequent machine cycles are prevented until the

failure is corrected, and no hazard is created by extending the

muted period).

Examples of Muting Sensors and Switches

Photoelectric Sensors (Opposed Mode): Opposed-mode

sensors, which initiate the muted condition when the beam path

is blocked, should be configured for dark operate (DO) and have

open (non-conducting) output contacts in a power OFF condition.

Both the emitter and receiver from each pair should be

powered from the same source, to eliminate common mode

failures.
Photoelectric Sensors (Polarized Retroreflective Mode): The

user must ensure that false “proxing” (activation due to shiny

or reflective surfaces) is not possible. Banner “LP” sensors with

linear polarization can greatly reduce or eliminate this effect.
Use a sensor configured for Light Operate (LO or N.O.) if

initiating a mute when the retroreflective target or tape is

detected (e.g., home position). Use a sensor configured for Dark

Operate (DO or N.C.) when a blocked beam path initiates the

muted condition (e.g., entry/exit). Both situations must have open

(non-conducting) output contacts in a power OFF condition.
Positive-Opening Safety Switches: Two (or four) independent

switches, each with a minimum of one closed safety contact to

initiate the mute cycle, are typically used. An application using

a single switch with a single actuator and two closed contacts

could result in an unsafe situation.
Inductive Proximity Sensors: Typically, inductive proximity

sensors are used to initiate a muted cycle when a metal surface

is detected. Due to excessive leakage current causing false ON

conditions, two-wire sensors are not to be used. Only three- or

four-wire sensors that have discrete PNP, NPN, or hard-contact

outputs that are separate from the input power can be used.

This manual is related to the following products: