4.47. I/O Complex Equipment ‘M7491_IP’
Description:
T7491 Multiplexed Input Module. The Multiplexed Input Module occupies one slot in
the Regent+Plus I/O chassis and provides two serial communications port interfaces to
remote multiplexed digital inputs. This module is used to declare a Matrix Driver Input
Unit. All data is presented in packed form.
Product Description reference: PD-T7035 Multiplexed I/O Module
OEM PARAMETERS:
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface module
is placed.
REGENT_CHASSI
S
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O where the
Module is placed.
PROC_ID
0 – 7
The matrix driver processor number that controls this input unit.
(This value selects which of the MDn parameters in the definition
of the T7491 module is used.)
UNIT_ID
0 – 3
Up to 4 Input/output units may be attached to each matrix driver.
This parameter is used to indicate the identity of this unit.
CONFIGURATION
PHYSICAL MODULE:
RACK 1:
4 ANALOGUE inputs
Variable 1:
Bit 0 is the state of channel 1. Bit 15 is the state of channel 16.
1 - channel high, 0 – channel low.
Variable 2:
Bit 0 is the state of channel 17. Bit 15 is the state of channel 32.
1 - channel high, 0 – channel low.
Variable 3:
Bit 0 is the state of channel 33. Bit 15 is the state of channel 48.
1 - channel high, 0 – channel low.
Variable 4:
Bit 0 is the state of channel 49. Bit 15 is the state of channel 64.
1 - channel high, 0 – channel low.
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.
3. The single input channel returned provides the T7491 board status.
4. The associated M7491 module MUST appear in the I/O configuration BEFORE this module.