I/o complex equipment ‘sx7411, Trusted, Tmr module t8160 – Rockwell Automation T8160 Trusted TMR Interface User Manual
Page 29
Trusted
TM
TMR Module T8160
Issue 13 May 13
PD-T8160
29
4.11. I/O Complex Equipment ‘SX7411’
Description:
T7411 Monitored Digital Input Module, 24V dc. The Monitored Digital Input Module
interfaces to 16 field input devices. The module performs line monitoring of the field
wiring connections and automatic testing of the input module electronics. The module
is designed to operate from field power ranging from 15V dc to 80V dc. This board
definition is used in a simplex configuration.
Product Description reference: PD-T7031 Monitored Digital Input Modules
OEM PARAMETERS:
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed.
REGENT_CHASSIS
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O
where the Module is placed.
MONITER_MASK
1 = mask fault LEDs
0 = enable fault LEDs
Entered as a 16 bit word. Bit 0 will mask channel 1,bit 15
will mask channel 16. This field will mask the
implementation of the fault LEDs on the module. Input
status is not affected.
OPEN_VOLTAGE
0 – 240
Voltage at which to indicate failure at switch open. The
data is entered in the form of a decimal number in the
range 0 - 255. However, 240 is the maximum the user
can enter to accommodate test ranges within the module.
ON_OFF_VOLTAGE
0 – 240
Voltage at which to indicate a transition from Low/High or
High/Low has taken place. It is again entered as a decimal
value the range 0 - 255, however 240 is the maximum the
user can enter to accommodate test ranges within the
module.
SHORT_VOLTAGE
0 – 240
Voltage at which to indicate failure at switch close. The
data is entered in the form of a decimal number in the
range 0 - 255. However, 240 is the maximum the user
can enter to accommodate test ranges within the module.