4.43. I/O Complex Equipment ‘DX7485’
Description:
T7485 Isolated Guarded Digital Output Module 24 to 120V ac/dc. The Isolated
Guarded Digital Output Module provides digitally switched outputs for controlling eight
field loads. The digital output circuits are ‘sourcing’ outputs that switch field power
ranging from 24 to 120V ac/dc. This board definition is used in a dual configuration.
Product Description reference: PD-T7034 Isolated Guarded Digital Output Module 24 to 120Vac/dc
OEM PARAMETERS:
OEM parameter
Valid numbers
Description
TICS_CHASSIS
TICS_SLOT
1 – 10
1 – 8 (Chassis 1)
1 – 12 (Expander
Chassis)
The TICS chassis & slot number where the TMR Interface
module is placed
REGENT_CHASSIS
REGENT_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O where the
first Module is placed.
PARTNER_CHASSIS
PARTNER_SLOT
1 – 16
1 – 10
The chassis & slot number within the Regent+Plus I/O where the
second Module is placed.
CONFIGURATION
PHYSICAL MODULE:
RACK 1:
8 BOOLEAN outputs
States to be written to the module identified by the OEM parameters.
Channel 1 is module channel 1 and Channel 8 is module channel 8.
TRUE – channel high, FALSE – channel low
RACK 2:
2 BOOLEAN input
Inputs reflecting the board status of the modules. Channel 1 is the first
module, channel 2 is the second module.
FALSE – board ok, TRUE – board fault
Notes:
1. All parameters must be supplied, even for virtual boards.
2. Trusted
TM
chassis and slot numbers start at 1, Regent+Plus I/O chassis and slot numbers
start at 1.
EXTRA INFORMATION
1. Writing to a channel of board 1 will cause physical writes to be made to both boards as
identified by the parameters associated with the board. Both boards must be managed by
the same TMR Interface.